PID Calculator
Type the gains of your PID controller (Kp, Ki, Kd, or Kc, Ti, Td) and the sample time. You get the controller output for a run of errors with its P, I and D parts at each step, the coefficients and difference equation to put in code, or the closed loop with your plant G(s) and its step response. To choose the gains for a process, use the PID tuning calculator.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use the PID calculator
- Choose the form of your gains: parallel (Kp, Ki in 1/s, Kd in s) or standard (Kc, Ti and Td in seconds).
- For The output for a run of errors type the sample time and the errors e = set point − measurement, one for each step (or paste a column of numbers).
- For Discrete coefficients and code you get b0, b1, b2, a1, a2 and lines of code to copy.
- For The closed loop with a plant G(s) type the plant as a numerator and a denominator, such as 1 and (s + 1)(s + 2).
- The box under the result works the coefficients and the output (or the closed-loop figures) out again on the server.
The PID formulas
- Parallel form: u = Kp e + Ki ∫e dt + Kd de/dt. Standard form: u = Kc (e + (1/Ti) ∫e dt + Td de/dt), so Kp = Kc, Ki = Kc ÷ Ti and Kd = Kc × Td.
- The D part is filtered: Kd s ÷ (Tf s + 1), with Tf = Td ÷ 10 unless you type it.
- Backward Euler (the usual code): P = Kp e[k]; I = I + Ki Ts e[k]; D = (Tf D + Kd (e[k] − e[k−1])) ÷ (Tf + Ts).
- Tustin: the integral adds Ki Ts (e[k] + e[k−1]) ÷ 2 and the filter uses (2Tf − Ts) and (2Tf + Ts).
- Difference equation: u[k] = b0 e[k] + b1 e[k−1] + b2 e[k−2] − a1 u[k−1] − a2 u[k−2].
Worked example
Kp = 2, Ki = 1 per s, Kd = 0.5 s, Ts = 0.1 s, Tf = 0.025 s, backward Euler: b0 = 6.1, b1 = −10.42, b2 = 4.4, a1 = −1.2, a2 = 0.2. For the errors 1, 0.8, 0.5, 0.3, 0.1, 0 the first output is 6.1 (P 2 + I 0.1 + D 4) and the last is −0.3316.
The same gains on G(s) = 1 ÷ ((s + 1)(s + 2)) give a closed loop that rises from 10 % to 90 % in 4.81 s without overshoot and settles in 9.71 s.
Limits you should know
- The controller starts from rest and has no output limits: a real controller clamps its output and stops integrating while clamped (anti-windup).
- The closed loop is continuous and linear: the sample time, valve limits and noise are left out.