Toolvito

Works on this device

Water Pressure Calculator

Water pressure in a building comes from the height of the water above a tap, or from a pump or the street main. Find the pressure from a tank height, turn a pressure into a head of water, find the pressure on another floor, the pressure left at a fixture while water flows, or the drawdown of a well pressure tank.

Enter your values

The static pressure at a tap, pipe or floor below a tank, a header tank or a column of water.

Your values

From the water level in the tank (or the top of the column) straight down to the tap, pipe or floor where you want the pressure.

More options

0 for a tank open to the air. For a closed or pressure tank, the gauge pressure of the air above the water.

998.2 kg/m³ is water at about 20 °C, an example. Hot water is a little lighter; the menu fills other examples.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose what you want to work out: pressure from a height, pressure to head, another floor, the residual pressure at a fixture, or pressure tank drawdown.
  2. Enter the heights and pressures you know and pick a unit for each: bar, psi, kPa, metres or feet.
  3. The water density starts at about 20 °C; you can change it under More options. Plumbing-code values are not built in: type your own.
  4. Choose Calculate. You can change the unit of each result, and the working shows each step.

The formulas

  • Pressure from a height: p = ρ × g × h. For water at about 20 °C that is 9.79 kPa for each metre, or 0.433 psi for each foot.
  • Head from a pressure: h = p ÷ (ρ × g). 1 bar holds up about 10.2 m (33.5 ft) of water.
  • Another floor: p₂ = p₁ − ρ × g × (height of the second point above the first).
  • Residual pressure at a fixture = static pressure − ρ × g × height − friction loss. The friction loss can be typed, or worked out with the Hazen-Williams formula for water.
  • Pressure tank drawdown (Boyle's law, absolute pressures): air volume = tank volume × precharge ÷ pressure; drawdown = air volume at cut-in − air volume at cut-out.

Worked examples

A tank whose water stands 10 m above a tap gives 998.2 × 9.80665 × 10 = 97,890 Pa: 0.979 bar or 14.20 psi. A header tank 3 m above a shower gives 0.294 bar (4.26 psi).

The ground floor has 4 bar. On a floor 9 m higher the static pressure is 4 − 0.881 = 3.119 bar. With no flow, 4 bar would lift water 40.86 m.

Residual pressure: 4 bar at the meter, a shower 6 m higher, 30 L/min through 25 m of copper tube of 20 mm inside diameter (C = 140). The height takes 0.587 bar and friction 0.402 bar, leaving 3.011 bar at the shower.

A 20 gallon well tank with a 38 psi precharge on a 40/60 switch gives a drawdown of 5.16 gallons (25.8% of the tank) at the standard atmosphere.

Limits you should know

  • The height choices give the static pressure, with no water flowing. Real pressure at a tap while it runs is lower: use the residual pressure choice.
  • Hazen-Williams is for water at ordinary temperatures in full pipes. Meters, valves, filters and backflow devices can lose much more than the pipe; add them or type the loss.
  • The least pressure a fixture needs, and pipe sizes, come from your plumbing code and the fixture maker; none is built in.
  • For pressure at a depth in a lake or the sea and level sensors, use the Hydrostatic Pressure Calculator. For pipe sizes and friction tables, use the Water Pipe Size Calculator.
  • The results are arithmetic for the values you type. They are not a design approval or professional advice.

Related tools