A 4-20 mA current loop sends a reading as a current: 4 mA at the bottom of the range and 20 mA at the top. This calculator turns a current into the reading and back, works out the voltage across a loop resistor, and checks that the loop supply is enough for the transmitter.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose what you want: current to value, value to current, the loop resistor, or the loop supply check.
- Type the range of the transmitter: the current and the value at the bottom and at the top, for example 4 mA = 0 bar and 20 mA = 10 bar. Other ranges, such as 0-20 mA, work the same way.
- Under More options you can type the lowest and highest valid currents your system uses. A current beyond them is shown as a fault.
- Choose Calculate.
The formulas
- Current to value: value = bottom value + (I − I bottom) ÷ (I top − I bottom) × (top value − bottom value).
- Percent of span = (I − I bottom) ÷ (I top − I bottom) × 100.
- Value to current: I = I bottom + (value − bottom value) ÷ (top value − bottom value) × (I top − I bottom).
- Loop resistor: V = I × R. For a 250 Ω resistor, 4 mA gives 1 V and 20 mA gives 5 V. The resistor for a voltage is R = V ÷ I top.
- Loop supply: the largest loop resistance = (supply − smallest transmitter voltage) ÷ highest current.
Worked examples
12 mA on a 0 to 10 bar transmitter: (12 − 4) ÷ 16 = 0.5 of the span, so the pressure is 5 bar.
−50 °C to 150 °C at 9.6 mA: (9.6 − 4) ÷ 16 = 0.35, so the temperature is −50 + 0.35 × 200 = 20 °C.
6.5 bar on the 0 to 10 bar transmitter needs 4 + 0.65 × 16 = 14.4 mA.
Resistor for 5 V at 20 mA: 5 ÷ 0.02 = 250 Ω, which gives 1 V at 4 mA.
Loop supply: 24 V and a transmitter that needs 12 V allow at most (24 − 12) ÷ 0.02 = 600 Ω in the loop at 20 mA. With 250 Ω, the transmitter gets 24 − 0.02 × 250 = 19 V.
Limits you should know
- The scaling is linear. A square-root signal (such as flow from a differential pressure) needs its own scaling.
- No fault limits of a standard are built in: type the ones your system uses. Many systems follow NAMUR recommendation NE 43, which uses 3.8 to 20.5 mA for valid readings and treats 3.6 mA or less, or 21 mA or more, as a fault. Check the edition and the setting of your transmitter.
- The smallest voltage a transmitter needs comes from its data sheet.
- This is arithmetic for checking a design. It is not professional advice; follow the data sheets and the rules for your plant, especially in hazardous areas.
- To read the resistor voltage with a converter, see the Adc Voltage Calculator. For a sensor with a voltage output, see the Sensor Voltage Scaling Calculator.