A pressure transducer sends a current or a voltage that rises in a straight line with the pressure. Turn a signal reading into a pressure, find the signal a pressure should give, or make a scaling table, for the range on the label of your transducer.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Convert.
Your result
How it was worked out
How to use this converter
- Choose what you want to do: signal to pressure, pressure to signal, or a scaling table.
- Choose the output signal of the transducer, such as 4 to 20 mA, 0 to 10 V or mV/V. For another range, choose Another range and type the signal at both ends.
- Type the pressure at the bottom and the top of the range from the label or data sheet, and say whether the transducer measures gauge, absolute or sealed gauge pressure. Try an example fills in example values.
- Enter the reading and choose Convert. The result shows the pressure, the percent of span, the state of the signal, and the pressure as gauge and absolute.
The formula
Pressure = bottom + (signal − signal at the bottom) ÷ (signal at the top − signal at the bottom) × (top − bottom). It is the straight line through the two range ends. Turned round: signal = signal at the bottom + (pressure − bottom) ÷ (top − bottom) × (signal span).
Ratiometric 0.5 to 4.5 V: the range is 10% to 90% of the supply, so the line moves with the supply voltage. mV/V bridge: the output in mV = excitation (V) × output in mV/V; the rated output is the mV/V at full scale.
Absolute = gauge + atmospheric pressure. A sealed gauge transducer reads against a pressure sealed inside it, so absolute = reading + sealed reference.
Worked examples
A 4 to 20 mA transducer for 0 to 10 bar gauge reads 12 mA: (12 − 4) ÷ (20 − 4) = 0.5 of the span, so the pressure is 5 bar gauge, or 6.013 bar absolute at the standard atmosphere.
A 0.5 to 4.5 V ratiometric sensor for 0 to 100 psi reads 2.5 V: 50 psi at a 5 V supply. If the supply is really 4.8 V, the range is 0.48 to 4.32 V and the same 2.5 V means 52.60 psi.
A bridge transducer of 2 mV/V for 0 to 200 bar, fed with 10 V, reads 10 mV: that is 1 mV/V, half the rated output, so 100 bar.
A 4 to 20 mA loop reads 3.5 mA. By NAMUR NE 43 that is a failure signal (3.6 mA or less), not a pressure.
Limits you should know
- The range ends and the rated output are your figures from the label, data sheet or calibration sheet. The example values are only for trying the tool and are not the data of any product.
- The line through two points does not include the errors of a real transducer (linearity, hysteresis, temperature, zero drift). For a multi-point calibration, use the points of its calibration sheet.
- NAMUR NE 43 is a convention, not a law: many systems use 3.8 to 20.5 mA for readings and 3.6 mA or less and 21 mA or more for failures. Check the limits of your system. A signal that starts at 0 (0 to 10 V, 0 to 20 mA) cannot tell a zero reading from a broken wire.
- For loop resistors and the loop supply, use the 4 to 20 mA Calculator. For a tank level from a pressure, use the Hydrostatic Pressure Calculator.
- The results are arithmetic for the values you type. They are not a calibration certificate or professional advice.