Add up the drainage fixture units (DFU) of the fixtures on a drain and find the smallest pipe whose limit in your code takes the total. You can also work out the waste water flow from discharge units by EN 12056-2, or read a flow from your code's table of fixture units.

Enter your values

The total load of the fixtures on a drain in fixture units, and the smallest pipe size whose limit takes it.

Your values
Fixtures on the drain

Drainage fixture units of one: the value your plumbing code gives for that fixture (for example a table of the UPC or the IPC). The boxes start empty; the example values are not taken from a code.

Pipe sizes and the most fixture units each takes (optional)

From the table of your code for this kind of drain (branch, stack or building drain, and its slope). The example limits are not taken from a code.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose what you want to work out: a fixture unit total and a pipe size, the EN 12056-2 waste water flow, or a flow from your code's table.
  2. Type each fixture with its fixture units (or discharge units) from your code, and how many there are. The boxes start empty: the tool holds no code values. Try an example fills in example values that are not taken from any code.
  3. To pick a pipe, type the pipe sizes and the most fixture units each takes, from the table of your code for this kind of drain.
  4. Choose Calculate. The tables show each fixture and each pipe size.

The formulas

  • Total load = Σ (fixture units of one fixture × how many).
  • Pipe size: the smallest of your sizes whose limit is at or above the total.
  • EN 12056-2 waste water flow: Qww = K × √ΣDU in l/s, with K the frequency factor. When the largest discharge unit of one appliance is more than Qww, that discharge unit is the flow. Qtot = Qww + Qc (continuous flows) + Qp (pumped flows).
  • Flow from your code's table: between two rows, flow = f1 + (f2 − f1) × (FU − FU1) ÷ (FU2 − FU1).

Worked examples

Two water closets at 4, three lavatories at 1, two showers at 2, one kitchen sink at 2 and one clothes washer at 3 (example values) add up to 8 + 3 + 4 + 2 + 3 = 20 fixture units. With example limits of 5, 18 and 120 for 2, 3 and 4 inch pipes, the 4 inch pipe is the smallest that takes 20.

By EN 12056-2, appliances with ΣDU = 8.3 l/s and K = 0.5 (example) give Qww = 0.5 × √8.3 = 1.44 l/s. A WC of 2.0 l/s is more than that, so the waste water flow is 2.0 l/s. Ten WCs at 2.0 and twenty basins at 0.5 give ΣDU = 30 and, with K = 0.7, Qww = 0.7 × √30 = 3.83 l/s.

A table with 14 gpm at 20 fixture units and 25 gpm at 50 gives, for 30 fixture units, 14 + 11 × 10 ÷ 30 = 17.67 gpm.

Limits you should know

  • Fixture unit values, discharge units, the frequency factor K, pipe size limits and flow tables come from the plumbing code in force where the work is done (for example the UPC, the IPC, or EN 12056-2 with its national annex). That code decides; this tool does not give the required values.
  • Fixture units are a load, not a flow, so they cannot be turned into gallons per minute by a fixed factor. Use the table or curve your code gives for drainage.
  • Codes also set smallest sizes for some fixtures, limits by slope and by kind of drain, and rules for vents. The tool does not check those.
  • The water supply side (water supply fixture units and the demand flow) is on the Plumbing Flow Demand Calculator. The slope of a drain is on the Plumbing Slope Calculator.
  • This is arithmetic for the values you type. Drainage must be designed to your local code and checked by a qualified person. It is not professional advice.