Lateral Load Distribution Calculator

Work out how much of a storey force each wall or frame takes. For a stiff (rigid) floor the page shares the force by stiffness and adds the twist about the centre of rigidity. For a flexible floor or roof it shares the force by tributary width.

Enter your values

For a concrete or other stiff floor: each wall takes a share by its stiffness, plus a share of the twist about the centre of rigidity.

Your values

Some codes ask for the force to be moved by a share of the building size (for example 5%) both ways. Type the distance from your code. The example is only for trying the tool.

Walls or frames

This unit is used in every row.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose Rigid diaphragm for a concrete or other stiff floor, or Flexible diaphragm for a timber floor or roof.
  2. Rigid: type each wall or frame, the direction it runs, its position (its x for a wall along y, its y for a wall along x) and its relative stiffness. Then type the force, its direction and the position of its line (the centre of mass).
  3. Type an extra (accidental) eccentricity from your code if it asks for one: the page adds it and takes it off.
  4. Flexible: type the position of each wall line, the length of the building and the load per length. Choose Calculate.

The formulas

  • Centre of rigidity: x_cr = Σ k x ÷ Σ k of the walls along y; y_cr = Σ k y ÷ Σ k of the walls along x.
  • Twist: for a force V along y on the line x_m, e = x_m − x_cr and M = V × e (anticlockwise positive). The torsional stiffness is J = Σ k (x − x_cr)² + Σ k (y − y_cr)².
  • Wall along the force: F = V × k ÷ Σk + M × k × (x − x_cr) ÷ J. Wall across the force: F = −M × k × (y − y_cr) ÷ J. A force along x works the same way with x and y swapped (M = −V × (y_m − y_cr)).
  • Flexible diaphragm: each wall line takes w × its tributary width, from halfway to the wall line on each side (to the end of the building for the first and the last).

Worked example

Walls along y at x = 0, 12 and 20 m have stiffness 2, 1 and 1; walls along x at y = 0 and 12 m have 1.5 each. Then x_cr = (2 × 0 + 12 + 20) ÷ 4 = 8 m, y_cr = 6 m and J = 2 × 8² + 4² + 12² + 2 × 1.5 × 6² = 396.

A force of 100 kN along y on the line x = 10 m has e = 2 m. With an extra eccentricity of 1 m, e = 3 m gives M = 300 kN·m: the wall at x = 0 takes 100 × 2 ÷ 4 − 300 × 2 × 8 ÷ 396 = 37.88 kN, and with e = 1 m it takes 45.96 kN, the larger value. The wall at x = 20 m takes 25 + 300 × 12 ÷ 396 = 34.09 kN.

With a flexible roof 20 m long carrying 5 kN/m to wall lines at 0, 8 and 20 m, the lines take 4 m, 10 m and 6 m of it: 20, 50 and 30 kN. The extra eccentricity of 1 m here is an example, not the rule of a code.

Limits you should know

  • The stiffnesses are relative numbers that you type, for example from the size of each wall or from a frame analysis. No load, code eccentricity or rule for when a diaphragm counts as rigid is built in.
  • The rigid model takes the floor as a stiff plate; the flexible model as simple spans between wall lines. Real floors are in between: codes say which model to use, and some designs check both.
  • The storey force itself (wind or earthquake) comes from your code. Overturning, the strength of the walls and drift are not checked here.
  • For the loads that reach columns, see the Column Load Calculator; for the forces in a braced frame, the Truss Member Force Calculator.
  • This is arithmetic for study and checking. It does not check a design: the engineer of record and the code in force decide. It is not professional advice.