Effective Length Calculator

Work out the effective length K × L of a column. Choose ideal end conditions, type your own factor K, or find K for a column in a rigid frame from the restraint factors G at its two ends.

Enter your values

K × L for one of the six ideal end conditions, or for a K that you type.

Your values

The unbraced length: the distance between the points that hold the column against moving sideways.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. For a simple column, choose Effective length for ideal end conditions, type the length and choose the ends. A table shows K × L for all six ideal cases.
  2. For a column in a frame, choose G at a joint and type the columns and beams that meet at the top joint; then do the same for the bottom joint.
  3. Choose K from the alignment chart equations, say whether the frame is braced or can sway, and type G at the top and the bottom. Choose Calculate.

The formulas

The two equations are printed in the Commentary on Appendix 7 of the AISC Specification for Structural Steel Buildings (ANSI/AISC 360-16), equations C-A-7-1 and C-A-7-2. They are the basis of the Jackson and Mooreland alignment charts. The page solves them by halving an interval until K is known to about 12 digits.

  • Effective length: K × L, the length of a pinned column that buckles at the same load.
  • Restraint factor at a joint: G = Σ(E I ÷ L) of the columns ÷ Σ(E I ÷ L) of the beams that meet there. G = 0 is a perfectly fixed end; a pinned end has a very large G.
  • Braced frame (sidesway inhibited): (G_A G_B ÷ 4)(π/K)² + ((G_A + G_B) ÷ 2)(1 − (π/K) ÷ tan(π/K)) + 2 tan(π ÷ 2K) ÷ (π/K) − 1 = 0, with K from 0.5 to 1.
  • Sway frame (sidesway uninhibited): (G_A G_B (π/K)² − 36) ÷ (6 (G_A + G_B)) − (π/K) ÷ tan(π/K) = 0, with K of 1 or more.

Worked example

A column 3 m long with both ends pinned has K × L = 3 m. With one end fixed and one pinned (K = 0.7 in theory), K × L = 2.1 m.

At a joint, two columns with I = 8,000 cm⁴ and L = 3.5 m meet two beams with I = 20,000 cm⁴ and spans of 6 m and 8 m. G = (2 × 8,000 ÷ 3.5) ÷ (20,000 ÷ 6 + 20,000 ÷ 8) = 4,571.4 ÷ 5,833.3 = 0.784.

With G_A = 1 at the top and G_B = 2 at the bottom, the braced frame equation gives K = 0.8133 and the sway frame equation K = 1.449. With G_A = G_B = 1 they give 0.7743 and 1.317. The sizes here are made up for the example.

Limits you should know

  • The theoretical factors are for ideal ends. Codes recommend larger design values where an end is fixed, and practical values of G for bases: type those yourself.
  • The alignment chart equations assume elastic columns, rigid joints and a regular frame in which all columns buckle together. The adjustments for beams with pinned or fixed far ends, and for inelastic columns, are not applied.
  • To use K × L, see the Euler Buckling Calculator, the Column Buckling Calculator and the Column Slenderness Calculator.
  • This is arithmetic for study and checking. It does not check a design: the engineer of record and the code in force decide. It is not professional advice.