Column Load Calculator
Work out the load that reaches a column from the roof and the floors above it. Type each level with its tributary area and its area loads; the page sums them from the top down. You can find the tributary area from the column spacing, and the axial stress in the column.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- If you do not know the tributary area, choose Tributary area of a column and type the distance to the next column on each side.
- Choose Column load from the levels it carries. Add a row for the roof and for each kind of floor, with its tributary area, its dead and live area loads and the number of such floors.
- Type the load factors of your code to get a factored load, and the area of the column to get the axial stress. Choose Calculate.
- The table shows the load in the column below each level. For buckling, take the load to the Column Buckling Calculator.
The formulas
- Tributary area: width = (left + right) ÷ 2, depth = (front + back) ÷ 2, area = width × depth. Each slab panel is shared equally by the columns at its corners.
- Load of a level: number of such levels × (tributary area × (dead load + live load) + other dead load at that level).
- Column load: the sum of the levels above. Factored load: γD × D + γL × L, with the factors of your code.
- Axial stress: σ = P ÷ A, the average stress over the column section.
Worked example
A column carries 30 m² of roof with 4 kPa dead and 1.5 kPa live load, and three floors of 30 m² with 5 kPa dead and 3 kPa live load, each floor with 8 kN of wall.
Roof: 30 × 4 = 120 kN dead and 30 × 1.5 = 45 kN live. Floors: 3 × (30 × 5 + 8) = 474 kN dead and 3 × 30 × 3 = 270 kN live. At the bottom D = 594 kN, L = 315 kN and D + L = 909 kN. With factors 1.2 and 1.6 the factored load is 1.2 × 594 + 1.6 × 315 = 1,216.8 kN.
With columns 6 m apart left and right and 5 m apart front and back, the tributary area is 6 × 5 = 30 m². A tube 219.1 mm outside and 200 mm inside has A = 6,287 mm², so 500 kN gives σ = 79.53 MPa. The loads and factors here are examples for trying the tool, not the values of a code.
Limits you should know
- No live load, load factor or load combination of a code is built in. Type the values of the code in force for the use of each floor, and work out each combination that applies.
- Live load reductions, wind, snow, earthquake and moments from beams that are off centre are not included. The column’s own weight counts only if you type it as an other dead load.
- The tributary rule suits a regular grid. Uneven spans, one-way slabs onto walls and continuous beams share loads in other ways.
- The axial stress is an average. For the load a column can carry, use the Column Buckling Calculator; for slenderness, the Column Slenderness Calculator. For the plate under the column, the Base Plate Calculator.
- This is arithmetic for study and checking. It does not check a design: the engineer of record and the code in force decide. It is not professional advice.