Pc Cooling Calculator

Find how much air must pass through a computer case to carry its heat away, and how warm that air gets. You enter the figures yourself: the power the parts draw, the ratings of your fans and cooler. The tool does not hold data about any product.

Enter your values

Find the airflow that carries a heat load away for a chosen temperature rise of the air, or solve the same relation for the rise or for the heat.

Your values

Almost all the electrical power that the parts draw becomes heat. Enter the power the computer draws under load.

How much warmer the air may leave the case than it enters.

More options

Dry air at 20 °C and 101.325 kPa has about 1.204 kg/m³. Air is thinner when it is hot or at high altitude.

Dry air near room temperature has about 1005 J/(kg·K).

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose what you want to work out, for example Airflow, heat and air temperature rise.
  2. Enter the heat to remove. It equals the electrical power the computer draws under load, because almost all of that power becomes heat.
  3. Enter the other figures from your specification sheets, and pick a unit for each one.
  4. Choose Calculate. You can change the unit of a result, copy it, or download it as a CSV file.

The formulas

  • Airflow: heat = air density × specific heat of air × airflow × temperature rise. So airflow = heat ÷ (density × specific heat × rise).
  • Case fans: the tool adds the rated airflow of the intake fans and of the exhaust fans. For the estimate it uses the smaller of the two totals, times the share of the rating you expect to get.
  • Cooler rating: margin = (cooler rating − processor power) ÷ processor power × 100.
  • Thermal resistance: part temperature = air temperature + power × thermal resistance. The resistance is in °C per watt.
  • Liquid loop: heat = coolant density × specific heat of the coolant × flow × temperature rise.

The air and water figures used

The starting values are for dry air at 20 °C and normal sea-level pressure, and for water at 25 °C. You can change them under More options, for example for thin air at high altitude or for a coolant mix.

Starting values of the fluid properties
Property Starting value Stated condition
Air density 1.204 kg/m³ Dry air, 20 °C, 101.325 kPa
Specific heat of air 1005 J/(kg·K) Dry air near room temperature
Water density 997 kg/m³ Water, 25 °C
Specific heat of water 4181 J/(kg·K) Water, 25 °C

Worked example

A computer draws 350 W under load, and the air may warm up by 10 °C on its way through the case. Airflow = 350 ÷ (1.204 × 1005 × 10) = 0.02893 m³/s. That is 104.1 m³/h, or 61.3 cubic feet per minute (CFM).

Now take two intake fans rated 55 CFM each and one exhaust fan rated 50 CFM. Intake is 110 CFM and exhaust is 50 CFM, so there is more intake than exhaust. With the smaller total of 50 CFM, the air warms up by about 12.3 °C for the same 350 W.

A cooler with a thermal resistance of 0.25 °C/W on a part that gives off 125 W, in air at 25 °C: 125 × 0.25 = 31.25 °C above the air, so the part is at 56.25 °C.

Limits you should know

  • The tool has no data about named coolers, fans, cases or processors. It only works with the numbers you type.
  • Rated fan airflow is measured in free air. In a case with filters, grilles and parts in the way the real airflow is lower. The tool cannot know by how much.
  • The air temperature rise is an average for all the air that passes through the case. A part in a spot with little air movement can be much warmer.
  • A cooler rating in watts is the maker's own figure. Two ratings from two makers do not compare exactly.
  • The thermal resistance option is a steady state with one resistance. It does not model short bursts of power or the resistances inside the part.
  • Results are for planning. Check the real temperatures with a monitoring program after you build.