Toolvito

Works on this device

Room Cfm Calculator

Find the air flow in cubic feet per minute (cfm) that a room needs: from the load the air must carry and the temperature difference of the supply air, from air changes per hour, or for the people in it.

Enter your values

The air flow (cfm) that carries a room's sensible load at a supply temperature difference, or the load a flow carries, or the temperature difference.

Your values

The sensible part of the load of the room (the BTU Calculator gives it). Latent heat (moisture) is not carried by a temperature difference.

Your design difference between the room air and the air from the supply grille. For cooling often about 15 to 20 °F; for warm air heating often more.

More options

The air properties are taken where the flow is measured, usually the supply air (for example about 55 °F for cooling).

Damp air is a little lighter than dry air. Type 0 for dry air.

Air is thinner high up, so the same flow carries less heat. The pressure is taken from the standard atmosphere for this height.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose Air flow from a heating or cooling load and type the sensible load of the room and the difference between the room air and the supply air. You can also find the load from a flow, or the temperature difference.
  2. For a whole house, choose Air flow for each room and add each room with its load. The tool splits the total air flow in proportion to the loads.
  3. For ventilation by air changes, choose Air flow from air changes per hour and type the room size.
  4. Under More options you can set the temperature, humidity and height above sea level of the air at the fan.
  5. Choose Calculate.

The formulas

  • Sensible heat: load = air flow × (specific heat ÷ specific volume) × temperature difference. With standard air: BTU/h = 1.08 × cfm × °F, or W = 1.2 × L/s × K.
  • Air flow = load ÷ (factor × temperature difference).
  • Each room: room air flow = total air flow × room load ÷ total load.
  • Air changes: air flow = room volume × air changes per hour ÷ 60 (cfm from cubic feet).
  • People: air flow = number of people × air for each person.
  • The room loads come from the BTU Calculator; the duct for each flow from the HVAC Duct Size Calculator.

Worked example

A room has a sensible cooling load of 12,000 BTU/h, and the supply air is 20 °F colder than the room. With supply air at 55 °F and 50% humidity at sea level, the factor is 1.112 BTU/h for each cfm and °F. The air flow is 12,000 ÷ (1.112 × 20) = 539 cfm.

With the familiar standard-air factor of 1.08 the same load needs 12,000 ÷ (1.08 × 20) = 556 cfm. Cold supply air is denser, so it carries a little more heat for each cfm.

Limits you should know

  • Only the sensible load is carried by the temperature difference. The moisture (latent) load of cooling is removed at the coil.
  • Splitting by load assumes every room needs air in proportion to its load. A room with a large heating load but a small cooling load can need a different share in summer and winter.
  • The tool has no table of ventilation rates for people or rooms. Use the rate from the standard or code that applies to you.
  • This is a first estimate, not a design (in the United States, ACCA Manual J gives the room loads and Manual D the room air flows for homes). This is not professional advice.

Related tools