BTU Calculator
Find how many BTU per hour a room or a whole house needs for heating or cooling. Add its walls, windows, doors, ceiling and floor with their insulation, and the tool adds the heat that leaks with the air, from people, from lights and from the sun.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose Heating load for a heater, furnace or boiler, or Cooling load for an air conditioner.
- Choose how you give the insulation: a US R-value (such as R-13 for a wall), a U-value, or a metric RSI value.
- Add a row for each surface that has outside air, a garage, a crawl space or the ground on the other side. Type its net area: take the windows and doors out of the wall they are in.
- Type the inside temperature you want and the outside design temperature for your place. For a surface next to a space at another temperature, type that temperature in its row.
- Type the floor area, the ceiling height and the air leakage in air changes each hour. For cooling, also type the people, the lights and equipment, and the sun on the windows.
- Choose Calculate. You get the load in BTU/h, watts, kW and tons, a table of where the heat goes, and the working.
The formulas
- Heat through a surface: Q = U × A × ΔT, where U is the U-value (U = 1 ÷ R), A the area and ΔT the difference between the inside and the other side.
- Air leakage: air flow = room volume × air changes each hour. Sensible heat = dry air mass flow × specific heat × ΔT. With standard air this is close to the familiar 1.08 × cfm × °F.
- Latent heat of leaking air (cooling): dry air mass flow × (humidity ratio outside − inside) × latent heat of water. Sensible and latent together are the change in enthalpy of the air.
- People, lights, equipment: the figures you type. Almost all electrical power used in a room ends up as heat.
- Sun through glass: area × solar heat gain coefficient (SHGC) × solar radiation on the glass.
- Units: 1 BTU/h = 0.29307 W, 1 kW = 3,412.14 BTU/h, 1 ton of refrigeration = 12,000 BTU/h = 3.517 kW.
- Water: heat = flow × density × specific heat × temperature drop; for water in US units about 500 × gpm × °F.
Worked example
A room of 200 ft² with an 8 ft ceiling has 180 ft² of R-13 wall, 40 ft² of windows at R-2, a 20 ft² door at R-2 and 200 ft² of R-30 ceiling. It is 70 °F inside and 10 °F outside, so ΔT is 60 °F.
Walls: 180 × (1 ÷ 13) × 60 = 831 BTU/h. Windows: 40 × 0.5 × 60 = 1,200 BTU/h. Door: 600 BTU/h. Ceiling: 200 × (1 ÷ 30) × 60 = 400 BTU/h. The surfaces lose 3,031 BTU/h.
Air leakage of 0.5 air changes each hour moves 1,600 × 0.5 ÷ 60 = 13.3 cfm, which takes 865 BTU/h. The heating load is about 3,896 BTU/h (1.14 kW), or 19.5 BTU/h for each square foot.
Rules of thumb (rough figures only)
The Rough estimate mode multiplies the floor area (or the room volume) by a figure that you choose. The list has examples that are often quoted, such as 20 BTU/h for each square foot for cooling, or 30 to 60 BTU/h for each square foot for heating from a mild to a very cold climate. They come from no standard and they ignore insulation, windows, sun and use, so the real load can be half or double. Use them only for a first idea.
Limits you should know
- Every U-value, temperature, air change rate and heat gain is your own figure. No climate data or building table is built in.
- Next steps: the Air Conditioner Size Calculator turns a cooling load into a unit size, the Radiator Sizing Calculator sizes radiators for a heat loss, the Room Cfm Calculator gives the air flow, and the Heating Cost Calculator the running cost.
- The steady-state formula does not count heat stored in walls, or the sun heating walls and roofs over the day. Methods such as the CLTD or RTS methods of the ASHRAE handbook do. You may type a higher temperature on the other side of a sunny roof.
- Heat lost to the ground through a slab or basement depends on the soil and the depth. Type the ground temperature you take, or a U-value for the whole floor.
- The air properties come from the inside temperature, humidity and height above sea level, using the moist air relations of the weather calculators.
- This is a first estimate, not a design. The size of heating or cooling equipment for a real building is decided by a professional load calculation, by the method used where you live (for example ACCA Manual J in the United States, or EN 12831 in Europe). This is not professional advice.