Radiator Sizing Calculator

Find what size of radiator a room needs. Enter the heat loss of the room and your water temperatures, and the tool gives the rated output to look for in the maker's table, corrected from its test conditions to yours.

Enter your values

The output the room needs, and the rated output (at ΔT50 or the ΔT of your maker's table) that each radiator must have to give it at your real water temperatures.

Your values

At your design outside temperature. The BTU Calculator works it out from the walls, windows and air leaks.

Your own allowance, for example for heating up after the heating was off. Type 0 for none.

The water temperature from the boiler or heat pump on a design day. Heat pumps often run at 35 to 55 °C.

The ΔT at which the maker gives the output. Today most makers use ΔT50 (75/65/20 °C under EN 442); older lists used ΔT60.

From the maker's data. About 1.3 is often given for panel radiators; check yours.

More options

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Work out the heat loss of the room first, for example with the BTU Calculator.
  2. Choose Radiator size for a room and type the heat loss in watts, kW or BTU/h, and how many radiators the room will have.
  3. Type the flow and return water temperatures on a design day and the room temperature. The example list has typical points for boilers and heat pumps.
  4. Check the ΔT of the maker's rating (most use ΔT50) and the radiator exponent n from the maker.
  5. Choose Calculate. Look for a radiator whose rated output in the maker's table is at least the figure shown.

The formulas

  • Mean temperature difference: ΔT = (flow + return) ÷ 2 − room, or the logarithmic mean (flow − return) ÷ ln((flow − room) ÷ (return − room)).
  • Output at your temperatures = rated output × (ΔT ÷ ΔT of the rating)^n.
  • Rated output to buy = output needed ÷ (ΔT ÷ ΔT of the rating)^n.
  • Sections = output needed ÷ output of one section at your temperatures, rounded up.
  • Steam: square feet of EDR = heat loss in BTU/h ÷ 240.
  • Water flow = output ÷ (specific heat × temperature drop).

Worked example

A room loses 1,500 W. The boiler runs at 70 °C flow and 60 °C return, and the room is at 20 °C, so ΔT = (70 + 60) ÷ 2 − 20 = 45 K.

With ΔT50 ratings and n = 1.3, the factor is (45 ÷ 50)^1.3 = 0.872. The radiator needs a rated output of 1,500 ÷ 0.872 = 1,720 W at ΔT50.

On a heat pump at 45 °C flow and 40 °C return, ΔT is 22.5 K and the factor 0.354, so the same room needs about 4,240 W at ΔT50: more than twice the size.

Limits you should know

  • The heat loss and the exponent are your figures. A wrong exponent changes the result most at low water temperatures.
  • The exponent rule is how radiators are tested (EN 442). Covers, shelves, curtains and paint can lower the output.
  • An electric radiator gives its rated watts at any setting: choose one with at least the output the room needs.
  • This is a first estimate. A heating engineer sizes radiators by the method used where you live (for example from an EN 12831 heat loss). This is not professional advice.