Works on this device
Air Changes per Hour Calculator
Find how many times each hour the air of a room is changed, or the air flow you need for a rate. The tool also gives the room size an air purifier can serve, the time to clear the air, and the air changes at 50 Pa from a blower door test.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose what you want to work out.
- Type the air flow (cfm, m³/h or L/s), and the room as length, width and height or as a volume.
- For a check, type the air changes per hour you need. Take that rate from the standard, code or guide for your kind of room; the tool has no table of rates.
- Choose Calculate. The working shows each step with your numbers.
The formulas
- Air changes per hour = air flow in one hour ÷ room volume. With cubic feet: ACH = cfm × 60 ÷ volume.
- Air flow = room volume × ACH ÷ 60 (cfm), or room volume × ACH (m³/h).
- Room an air purifier serves: volume = CADR × 60 ÷ ACH; floor area = volume ÷ ceiling height.
- Clearing the air (perfect mixing): the share of old air left after t hours is e^(−ACH × t). So 99% is gone after ln(100) = 4.6 air changes, and 99.9% after 6.9.
- Air tightness: ACH50 = flow at 50 Pa × 60 ÷ volume; from an air permeability q50, n50 = q50 × envelope area ÷ volume.
- For the outdoor air that people and floor area need, use the Ventilation Calculator; for the air flow that carries a heating or cooling load, the Room Cfm Calculator.
Worked example
A room is 15 ft × 12 ft with an 8 ft ceiling, so its volume is 1,440 ft³. A fan supplies 200 cfm. ACH = 200 × 60 ÷ 1,440 = 8.33 air changes per hour, one every 7.2 minutes.
For 6 air changes per hour the same room needs 1,440 × 6 ÷ 60 = 144 cfm. At 6 air changes per hour, clearing 99% of a smell takes 4.6 air changes, which is 46 minutes.
Limits you should know
- The tool does not tell you how many air changes a room needs. Hospitals, clean rooms, labs, kitchens, offices, homes and confined spaces have rates set by standards and rules (such as ASHRAE, CIBSE or the rules where you work); use those.
- Air does not replace itself in one air change: it mixes. The purge time assumes perfect mixing; real rooms can take longer.
- A fan or purifier gives less air than its label when it works against ducts and filters. Measure the flow if it matters.
- Dividing ACH50 by a number such as 20 gives only a rough idea of everyday leakage.
- The ventilation of a real building, and the size of its fans and equipment, is decided by a professional design by the method and code used where you live.
- For confined spaces, follow the entry rules where you work and test the air. This tool is not a safety check, and it is not professional advice.