Find how many times each hour the air of a room is changed, or the air flow you need for a rate. The tool also gives the room size an air purifier can serve, the time to clear the air, and the air changes at 50 Pa from a blower door test.

Enter your values

How many times each hour a flow of air changes the air of a room. With a required rate you can check whether the flow is enough.

Your values

The air supplied to the room or taken out of it (use the larger of the two), or the clean air delivery rate (CADR) of an air purifier.

You can type feet and inches, such as 15 ft 6 in.

The rate from the standard or guide that applies to your room. The tool then checks the flow against it.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose what you want to work out.
  2. Type the air flow (cfm, m³/h or L/s), and the room as length, width and height or as a volume.
  3. For a check, type the air changes per hour you need. Take that rate from the standard, code or guide for your kind of room; the tool has no table of rates.
  4. Choose Calculate. The working shows each step with your numbers.

The formulas

  • Air changes per hour = air flow in one hour ÷ room volume. With cubic feet: ACH = cfm × 60 ÷ volume.
  • Air flow = room volume × ACH ÷ 60 (cfm), or room volume × ACH (m³/h).
  • Room an air purifier serves: volume = CADR × 60 ÷ ACH; floor area = volume ÷ ceiling height.
  • Clearing the air (perfect mixing): the share of old air left after t hours is e^(−ACH × t). So 99% is gone after ln(100) = 4.6 air changes, and 99.9% after 6.9.
  • Air tightness: ACH50 = flow at 50 Pa × 60 ÷ volume; from an air permeability q50, n50 = q50 × envelope area ÷ volume.
  • For the outdoor air that people and floor area need, use the Ventilation Calculator; for the air flow that carries a heating or cooling load, the Room Cfm Calculator.

Worked example

A room is 15 ft × 12 ft with an 8 ft ceiling, so its volume is 1,440 ft³. A fan supplies 200 cfm. ACH = 200 × 60 ÷ 1,440 = 8.33 air changes per hour, one every 7.2 minutes.

For 6 air changes per hour the same room needs 1,440 × 6 ÷ 60 = 144 cfm. At 6 air changes per hour, clearing 99% of a smell takes 4.6 air changes, which is 46 minutes.

Limits you should know

  • The tool does not tell you how many air changes a room needs. Hospitals, clean rooms, labs, kitchens, offices, homes and confined spaces have rates set by standards and rules (such as ASHRAE, CIBSE or the rules where you work); use those.
  • Air does not replace itself in one air change: it mixes. The purge time assumes perfect mixing; real rooms can take longer.
  • A fan or purifier gives less air than its label when it works against ducts and filters. Measure the flow if it matters.
  • Dividing ACH50 by a number such as 20 gives only a rough idea of everyday leakage.
  • The ventilation of a real building, and the size of its fans and equipment, is decided by a professional design by the method and code used where you live.
  • For confined spaces, follow the entry rules where you work and test the air. This tool is not a safety check, and it is not professional advice.