Work out how much outdoor air a space needs from the rates of your standard, how much vent area an attic or roof needs by the net free area rule of your code, and how much air flows through windows and vents without a fan.

Enter your values

The outdoor (fresh) air a space needs: rate for each person × people + rate for each unit of area × floor area, ÷ air distribution effectiveness. With the heat to warm that air and the saving of heat recovery.

Your values

From the ventilation standard or code that applies to the room. The list above has labelled examples only.

From the same standard or code, in the unit below.

How well the supply air reaches the breathing zone (Ez in ASHRAE 62.1). 1 means fully. Take the figure for your supply and return layout from your standard.

More options

With the outside temperature it gives the heat needed to warm (or cool) the outdoor air.

The design temperature for your place; no climate figure is built in.

The sensible efficiency of a heat recovery ventilator (HRV, ERV, MVHR) from its data sheet.

Damp air is a little lighter than dry air. Type 0 for dry air.

Air is thinner high up, so the same flow carries less heat. The pressure is taken from the standard atmosphere for this height.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose Outdoor air for people and floor area, Attic and roof vents or Natural ventilation.
  2. For outdoor air, type the people and the floor area, and the two rates from the ventilation standard or code that applies to you. The menu has labelled examples; check them against your standard.
  3. For an attic, type the attic floor area and the ratio of your code (such as 1 in 150). Add the net free area of the vents you plan to use, from their maker, to get the number of vents or the length of ridge vent.
  4. For natural ventilation, choose the stack effect or wind, and type the openings and the temperatures or the wind speed.
  5. Choose Calculate.

The formulas

  • Outdoor air = (rate for each person × people + rate for each unit of area × floor area) ÷ air distribution effectiveness.
  • Heat of the outdoor air = flow × sensible heat factor × temperature difference; with heat recovery, × (1 − efficiency).
  • Attic vents: net free area = attic floor area ÷ ratio (for example ÷ 150), split between intake (low) and exhaust (high). Vents = area needed ÷ net free area of one vent, rounded up.
  • Stack effect: Q = Cd × A × √(2 × g × h × ΔT ÷ T), with the effective area A of the low and high openings in series.
  • Wind: Q = Cv × A × wind speed.
  • To move the air with a fan, the Fan Electricity Cost Calculator gives the fan power and running cost, and the HVAC Duct Size Calculator the duct size.

Worked example

An attic floor of 1,500 ft² with the 1 in 150 rule needs 1,500 ÷ 150 = 10 ft² = 1,440 in² of net free area: 720 in² of intake and 720 in² of exhaust. With soffit vents of 9 in² each, that is 80 vents; with a ridge vent of 18 in² for each foot, 40 ft of ridge vent.

An office of 2,000 ft² with 20 people, at the example rates of 5 cfm for each person and 0.06 cfm for each ft², needs 100 + 120 = 220 cfm of outdoor air.

Limits you should know

  • No ventilation rate or code ratio is built in. The examples in the menus are labelled; check the edition of the standard your code uses.
  • Combustion air for boilers and gas appliances follows the gas code and the appliance maker, and smoke ventilation is fire engineering. This tool does not do them.
  • Natural ventilation changes with the weather; the figures hold only for the temperatures and wind you typed.
  • This is a first estimate, not a design. Follow your building code and the makers, and ask a professional for a real building. This is not professional advice.