HVAC Duct Size Calculator
Find the size of an air duct for a heating, cooling or ventilation system. Enter the air flow and the friction rate (or velocity) you design for, and get the round size, a rectangular size of the same friction, and the velocity.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose Duct size from air flow and friction rate to work like a duct calculator wheel, or Duct size from air flow and velocity.
- Type the air flow in cfm, m³/h or L/s, and your design friction rate or velocity.
- To get a rectangular duct, type the height (or width) that fits your space. To round up to sizes you can buy, type your list of round sizes.
- Under More options you can change the roughness of the duct and the temperature, humidity and height above sea level of the air.
- Choose Calculate. The other modes give the equivalent round size of a rectangular or flat oval duct, rectangular sizes for a round size, a cfm chart for a list of sizes, and the pressure loss of a run.
The formulas
- Velocity: V = air flow ÷ area; the area of a round duct is π × D² ÷ 4.
- Friction: Darcy-Weisbach, Δp ÷ L = f × ρ × V² ÷ (2 × D), with the friction factor from the Colebrook relation 1 ÷ √f = −2 × log10(ε ÷ (3.7 D) + 2.51 ÷ (Re × √f)). Re = ρ × V × D ÷ μ.
- Air: density from the moist air relations at your temperature, humidity and height; viscosity by Sutherland's law.
- Rectangular duct: equivalent round diameter for the same friction and flow, De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25 (Huebscher).
- Flat oval duct: De = 1.55 × A^0.625 ÷ P^0.25, with the area A = π b² ÷ 4 + b (a − b) and the perimeter P = π b + 2 (a − b).
- Fittings: loss = loss coefficient C × velocity pressure, where velocity pressure = ρ × V² ÷ 2.
- The air flow of each room comes from the Room Cfm Calculator; the fan power and running cost at the pressure loss from the Fan Electricity Cost Calculator.
Worked example
A supply duct carries 400 cfm. At a friction rate of 0.1 inches of water for each 100 ft, with galvanized steel (roughness 0.09 mm) and air at 68 °F, the tool gives a round duct of 9.68 in with a velocity of 783 fpm. From a list of whole-inch sizes it takes 10 in, where the velocity is 733 fpm and the friction rate 0.085 in. w.g. for each 100 ft.
A rectangular duct 12 in × 8 in has the same friction as a round duct of 10.66 in. At 400 cfm its velocity is 600 fpm.
Limits you should know
- Standard sizes are only the list you type; the tool has no catalogue of duct sizes.
- The roughness figures in the examples are rough. Flexible duct that is not pulled tight, or that has sharp bends, loses far more than straight duct.
- Charts printed on duct calculator wheels were drawn for their own air, roughness and joints, so they can differ by a few percent.
- The friction relation of duct design is for turbulent flow. The tool refuses sizes where the flow would not be turbulent.
- A duct system needs the fan, every branch, the fittings and the grilles worked out together. This is a first estimate, not a design (in the United States, ACCA Manual D is one method used for homes). This is not professional advice.