HVAC Duct Size Calculator

Find the size of an air duct for a heating, cooling or ventilation system. Enter the air flow and the friction rate (or velocity) you design for, and get the round size, a rectangular size of the same friction, and the velocity.

Enter your values

The method of a duct calculator wheel (ductulator): the round size that carries the air flow at the friction rate you choose, and a rectangular size of the same friction.

Your values

The air this duct must carry, from the room air flows (the Room Cfm Calculator works them out).

The pressure loss you allow for each length of straight duct. Your own design figure; 0.08 to 0.1 in. w.g. for each 100 ft is often used for homes.

Type the height (or width) that fits your space, and the tool gives the other side.

Your own list of diameters, separated by commas, in the unit below. The tool then picks the next size up.

More options

The absolute roughness ε. 0.09 mm (0.0003 ft) is the figure often used for galvanized steel duct. A flexible duct that is not pulled straight loses much more than any figure here.

The temperature of the air in the duct. Density and viscosity are taken at this temperature.

Damp air is a little lighter than dry air. Type 0 for dry air.

Air is thinner high up, so the same flow carries less heat. The pressure is taken from the standard atmosphere for this height.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose Duct size from air flow and friction rate to work like a duct calculator wheel, or Duct size from air flow and velocity.
  2. Type the air flow in cfm, m³/h or L/s, and your design friction rate or velocity.
  3. To get a rectangular duct, type the height (or width) that fits your space. To round up to sizes you can buy, type your list of round sizes.
  4. Under More options you can change the roughness of the duct and the temperature, humidity and height above sea level of the air.
  5. Choose Calculate. The other modes give the equivalent round size of a rectangular or flat oval duct, rectangular sizes for a round size, a cfm chart for a list of sizes, and the pressure loss of a run.

The formulas

  • Velocity: V = air flow ÷ area; the area of a round duct is π × D² ÷ 4.
  • Friction: Darcy-Weisbach, Δp ÷ L = f × ρ × V² ÷ (2 × D), with the friction factor from the Colebrook relation 1 ÷ √f = −2 × log10(ε ÷ (3.7 D) + 2.51 ÷ (Re × √f)). Re = ρ × V × D ÷ μ.
  • Air: density from the moist air relations at your temperature, humidity and height; viscosity by Sutherland's law.
  • Rectangular duct: equivalent round diameter for the same friction and flow, De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25 (Huebscher).
  • Flat oval duct: De = 1.55 × A^0.625 ÷ P^0.25, with the area A = π b² ÷ 4 + b (a − b) and the perimeter P = π b + 2 (a − b).
  • Fittings: loss = loss coefficient C × velocity pressure, where velocity pressure = ρ × V² ÷ 2.
  • The air flow of each room comes from the Room Cfm Calculator; the fan power and running cost at the pressure loss from the Fan Electricity Cost Calculator.

Worked example

A supply duct carries 400 cfm. At a friction rate of 0.1 inches of water for each 100 ft, with galvanized steel (roughness 0.09 mm) and air at 68 °F, the tool gives a round duct of 9.68 in with a velocity of 783 fpm. From a list of whole-inch sizes it takes 10 in, where the velocity is 733 fpm and the friction rate 0.085 in. w.g. for each 100 ft.

A rectangular duct 12 in × 8 in has the same friction as a round duct of 10.66 in. At 400 cfm its velocity is 600 fpm.

Limits you should know

  • Standard sizes are only the list you type; the tool has no catalogue of duct sizes.
  • The roughness figures in the examples are rough. Flexible duct that is not pulled tight, or that has sharp bends, loses far more than straight duct.
  • Charts printed on duct calculator wheels were drawn for their own air, roughness and joints, so they can differ by a few percent.
  • The friction relation of duct design is for turbulent flow. The tool refuses sizes where the flow would not be turbulent.
  • A duct system needs the fan, every branch, the fittings and the grilles worked out together. This is a first estimate, not a design (in the United States, ACCA Manual D is one method used for homes). This is not professional advice.