Toolvito

Works on this device

Fan Electricity Cost Calculator

Find the electricity a fan uses and what it costs. You type the power of your own fan and your own price for one kWh: none is built in. The costs are estimates from the figures you type.

Enter your values

What a ceiling fan, a pedestal fan, an exhaust fan or any other fan costs to run for an hour, a day, a month and a year.

Your values

The electrical power that the fan takes in, from its label or data sheet. A fan with several speeds uses less on the low ones: type the watts of the speed you use. No typical value is built in.

The unit rate on your bill or tariff sheet, in the main unit of your money: type 0.15 for 15 cents. No price is built in.

More options

For a machine that runs in one season only. Leave it empty for use all year.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose Running cost of a fan from its power.
  2. Type the power of the fan in watts, from its label or data sheet, and how many such fans you have.
  3. Type the hours that the fan runs each day and the days each week.
  4. Type your electricity price for one kWh, from your bill.
  5. Choose Calculate. Try an example fills the empty boxes with example values, so that you can see how an option works.

What each option does

  • Running cost from the power: the energy and the cost for an hour, a day, a month and a year.
  • Fan power and cost from air flow and pressure: for a ventilation or process fan, the air power, the shaft power and the input power from the efficiencies you type, and the running cost.
  • Cost at a new fan speed: the power, the air flow and the pressure at another speed by the affinity laws, and the cost at both speeds.

The formulas

  • Energy in kWh = input power in kW × hours of running. Cost = energy × price for one kWh.
  • Running hours in a year = hours each day × days each week × 365 ÷ 7, or × the weeks you type.
  • Air power = air flow × pressure rise. One m³/s against 1,000 Pa is 1 kW.
  • Input power = air power ÷ efficiency of the fan ÷ efficiency of the motor and drive.
  • Specific fan power = input power ÷ air flow.
  • Affinity laws for the same fan in the same ducts: flow changes in step with the speed, pressure with the square of the speed, and power with the cube of the speed.

Worked examples

Running cost. A fan of 75 W runs 8 hours a day, every day. It uses 0.6 kWh a day and 219 kWh a year. At 0.15 for one kWh, that is 0.09 a day, 2.74 a month and 32.85 a year.

Air flow and pressure. A fan moves 10,000 m³/h against 500 Pa. The air power is 2.7778 m³/s × 500 Pa = 1,388.9 W. With a fan efficiency of 65% and a motor and drive efficiency of 90%, the input power is 1,388.9 ÷ 0.65 ÷ 0.90 = 2,374.2 W. For 8 hours a day that is 6,932.57 kWh a year, which costs 1,039.89 at 0.15 for one kWh.

A new speed. A fan takes in 5.5 kW at 1,450 revolutions per minute. At 1,160 revolutions per minute the speed ratio is 0.8, so the power is 5.5 × 0.8³ = 2.816 kW. The air flow falls from 10,000 to 8,000 m³/h. For 8 hours a day the cost falls from 2,409.00 to 1,233.41 a year, a saving of 1,175.59.

Where to find your figures

  • Power of the fan: the label or the data sheet, or a plug-in power meter. A fan with several speeds has a lower power on the low speeds.
  • Air flow, pressure rise and fan efficiency: the fan curve in the data sheet at your working point, or measurements.
  • Efficiency of the motor and drive: the rating plate of the motor and the data of the belt or the speed drive.
  • Electricity price for one kWh: the unit rate on your bill.
  • The values that Try an example fills in are for trying the tool. They are not the data of any real fan and not current prices.

Limits you should know

  • The power on a label is for one speed and one working point. A measured power is the better figure.
  • The affinity laws are an ideal model. They take the same fan, the same ducts with nothing opened or closed, and the same air. The efficiency of the motor and the drive falls at low speed, so the real saving is a little smaller.
  • A slower fan moves less air. Check that the room or the process still gets the air it needs.
  • Air power = flow × pressure rise takes the air as not compressed. This holds for fans, not for blowers and compressors.
  • To compare two fans, or to find the payback of a speed drive, use the motor energy savings calculator.
  • Only the energy is priced. Standing charges, a demand charge and tax are not counted.
  • Costs for a month and a year are rounded once to 2 decimal places, and a half is rounded away from zero. The costs are estimates, not a bill, and the tool does not choose a fan or a motor.