Exhaust Fan Calculator

Find how much air an exhaust fan must move. Choose how your code or guide gives the rate: for each square foot of floor, as air changes per hour, or for each foot of a kitchen hood. Then type the size of the room or the hood.

Enter your values

Air flow = floor area × your rate for each unit of floor area.

Your values

Of the room, or of the attic floor for an attic fan, or of the living space for a whole house fan.

Your rate, from the code or guide that applies to the room. The menu above has rough examples only.

From the label, at the static pressure of your duct. The tool then counts how many fans you need.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose By floor area for a rate for each square foot or square metre, such as for a bathroom, an attic or a whole house fan.
  2. Choose By air changes per hour for a rate in air changes, such as for a bathroom, a kitchen, a toilet room or a workshop. Type the room size or its volume.
  3. Choose Kitchen hood for a rate for each foot or metre of the hood.
  4. Type your rate, or pick a rough example from the menu and check it against your code.
  5. Add the flow of one fan if you want to know how many fans you need. Then choose Calculate.

The formulas

  • By floor area: air flow = floor area × rate for each unit of floor area.
  • By air changes: air flow (cfm) = room volume (ft³) × air changes per hour ÷ 60. In metric: m³/h = room volume (m³) × air changes per hour.
  • Kitchen hood: air flow = hood length × rate for each unit of length.
  • Fans needed = air flow needed ÷ flow of one fan, rounded up.

Worked example

A bathroom of 8 ft × 10 ft has 80 ft² of floor. At the rough example of 1 cfm for each ft², the fan must move 80 cfm (136 m³/h).

By air changes: the same room with an 8 ft ceiling holds 640 ft³. At 8 air changes per hour the fan must move 640 × 8 ÷ 60 = 85.3 cfm.

A 30 inch hood on a wall at the rough example of 100 cfm for each foot needs 2.5 × 100 = 250 cfm.

Limits you should know

  • No rate of any code is built in. The examples in the menus are rough figures that are often quoted; codes and guides (such as ASHRAE 62.2, the residential code, or Approved Document F in England) set the rates where you live.
  • A fan gives less than its free-air rating against the static pressure of its duct. Choose a fan by its flow at your static pressure; the HVAC Duct Size Calculator gives the pressure loss of a duct run.
  • For the air flow a room needs to carry heat, use the Room Cfm Calculator. For fresh air rates for people and floor area, use the Ventilation Calculator.
  • Smoke exhaust and smoke control are fire safety systems designed by an engineer to the fire code; this tool does not size them.
  • This is a first figure from your rate, not a design. The fan for a real building is chosen by a professional by the code or method used where you live.