Duct Velocity Calculator
Find how fast air moves in a duct, or how much air a duct carries at a velocity. The tool also turns a pitot tube reading into a velocity, sizes grilles by face velocity, and averages readings across a duct.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose what you want: the velocity from the air flow, the air flow from the velocity, a pitot reading, a grille, or a traverse.
- Choose the shape of the duct and type its inside size. A flat oval duct has a width (major axis) and a height (minor axis).
- Type the air flow (cfm, m³/h, L/s) or the velocity (ft/min, m/s).
- Under More options you can set the air temperature, humidity and height above sea level. They change the air density and so the velocity pressure.
- Choose Calculate. The working shows each step with your numbers.
The formulas
- Velocity = air flow ÷ area. Round: area = π × D² ÷ 4. Rectangular: width × height. Flat oval: π b² ÷ 4 + b × (a − b).
- Air flow = velocity × area.
- Velocity pressure: Pv = ρ × V² ÷ 2, so V = √(2 × Pv ÷ ρ). For standard air (0.075 lb/ft³) this is V (fpm) = 4005 × √(Pv in in. w.g.).
- Grille: velocity through the free area = air flow ÷ (face area × free area share).
- Traverse: air flow = average of the velocities at evenly spread points × area. Pressure readings are turned into velocities before they are averaged.
- To size a duct for a velocity or a friction rate, use the HVAC Duct Size Calculator; it gives the same velocity for the same duct.
Worked example
400 cfm in a 10 in round duct: the area is π × 10² ÷ 4 = 78.54 in² = 0.5454 ft². The velocity is 400 ÷ 0.5454 = 733.4 ft/min (3.73 m/s).
With air at 68 °F, 50% humidity at sea level (0.0748 lb/ft³), the velocity pressure is 0.0334 in. w.g. (8.32 Pa).
A pitot reading of 0.05 in. w.g. in the same air means a velocity of 897 ft/min; the standard-air rule 4005 × √0.05 gives 896 ft/min.
Limits you should know
- The velocity here is the mean over the section. Near the walls the air is slower and in the middle it is faster.
- Grille throw, noise and pressure loss come from the maker's tables, not from this tool.
- For a reliable traverse the measuring points must follow a traverse standard and be far enough from bends and fittings.
- The velocities and sizes are physics with your figures. Design velocities for quiet ducts and grilles are your own choice.
- The duct system and the equipment of a real building are sized by a professional design by the method used where you live. This is not professional advice.