Thermal Resistance Calculator

Work out the thermal resistance of a layer, a surface film or a contact, and add them up in series or in parallel. You get the R-value in RSI and US units, the U-value and, with two temperatures, the heat flow and the temperature at each face.

Enter your values

R = L ÷ (k × A) for a flat layer; the pipe and ball forms for round layers.

Your values

0.04 W/(m·K) is an example for mineral wool. Use the value for your material, or fill in an example from the menu above.

Type 1 m² to get the figures for each square metre.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose what you want: one layer from its conductivity, the conductivity from a resistance, a surface film or a contact, parts in series, paths side by side, or a conversion of R-values and U-values.
  2. Enter the values you know, with their units. For parts in series, add one row for each layer, surface film or part with a known R-value, from one side to the other.
  3. Choose Calculate. The result shows the resistance, the R-value and U-value, and the working. A table lists each part and its share.

The formulas

  • Flat layer: R = L ÷ (k × A). Its R-value (for each square metre) is L ÷ k.
  • Pipe layer: R = ln(r2 ÷ r1) ÷ (2π × k × ℓ). Ball layer: R = (1 ÷ r1 − 1 ÷ r2) ÷ (4π × k).
  • Surface film: R = 1 ÷ (h × A). Contact: R = R″ ÷ A, or 1 ÷ (h_c × A).
  • In series: R = R1 + R2 + … . In parallel: 1 ÷ R = 1 ÷ R1 + 1 ÷ R2 + … .
  • U-value = 1 ÷ R-value. Heat flow Q = ΔT ÷ R, or U × A × ΔT for a flat wall.
  • US R-value: 1 ft²·°F·h/BTU = 0.176110 m²·K/W, so an RSI of 1 m²·K/W is a US R-value of 5.67826.

Worked examples

A layer of mineral wool 100 mm thick with k = 0.04 W/(m·K): R-value = 0.1 ÷ 0.04 = 2.5 m²·K/W, which is a US R-value of 14.1957. On 1 m² its resistance is 2.5 K/W.

A wall with an inside surface resistance of 0.13 m²·K/W, 220 mm of brick (k = 0.72), 100 mm of mineral wool (k = 0.04) and an outside surface resistance of 0.04: R-value = 0.13 + 0.305556 + 2.5 + 0.04 = 2.97556 m²·K/W, so U = 0.336072 W/(m²·K). With 20 °C inside and 0 °C outside, 6.72143 W flows through each square metre.

Limits you should know

  • Steady state, heat flowing straight through each part. Corners, fixings and other thermal bridges are not modelled; the parallel paths choice gives a simple estimate for studs.
  • Surface coefficients, contact resistances and R-values of products are your own figures. The Convection Calculator works out a surface coefficient from a flow.
  • The example surface resistances (0.13 and 0.04 m²·K/W) and example conductivities are for trying the tool; use the figures that apply to your case.
  • For the heat flow, a face temperature or a thickness of one layer, see the Conduction Calculator. For the heat lost through a wall over a time and its cost, see the Heat Loss Calculator; for the insulation needed for a target, the Insulation Thickness Calculator.
  • This is arithmetic for learning and checking, not a building regulation calculation.