Conduction Calculator
Work out how much heat is conducted through a solid layer by Fourier's law. Choose a flat wall, a pipe wall or pipe insulation, a spherical shell, or several layers in a row. You can find the heat flow, a face temperature, the thickness or the thermal conductivity.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose the shape: a flat wall, a pipe (cylindrical layer), a spherical shell, or several layers in a row.
- Choose what you want to find: the heat flow, the temperature of one face, the thickness or the thermal conductivity k.
- Enter what you know. The temperatures are those of the two surfaces of the layer. You can fill in a rounded example conductivity from the menu.
- Choose Calculate. The result shows the heat flow, the heat flux, the thermal resistance and the working. Change the unit of a result with its menu.
The formulas (Fourier's law)
- Flat wall: Q = k × A × (T1 − T2) ÷ L. The thermal resistance is R = L ÷ (k × A).
- Pipe wall or pipe insulation: Q = 2π × k × ℓ × (T1 − T2) ÷ ln(r2 ÷ r1), with r1 the inner and r2 the outer radius and ℓ the length. R = ln(r2 ÷ r1) ÷ (2π × k × ℓ).
- Spherical shell: Q = 4π × k × (T1 − T2) ÷ (1 ÷ r1 − 1 ÷ r2). R = (1 ÷ r1 − 1 ÷ r2) ÷ (4π × k).
- Several layers: the resistances add up, R = R1 + R2 + …, and Q = (T1 − T2) ÷ R. The temperature falls by Q × R across each layer.
- Heat flux is the heat flow for each square metre of area: q = Q ÷ A.
Worked examples
A flat layer of mineral wool 50 mm thick (k = 0.04 W/(m·K)) has an area of 10 m². One face is at 60 °C and the other at 20 °C. R = 0.05 ÷ (0.04 × 10) = 0.125 K/W, so Q = 40 ÷ 0.125 = 320 W, and the heat flux is 32 W/m².
The same insulation, 50 mm thick, around a pipe with an outside diameter of 60.3 mm, for 1 m of pipe: r1 = 0.03015 m and r2 = 0.08015 m. R = ln(0.08015 ÷ 0.03015) ÷ (2π × 0.04 × 1) = 3.89022 K/W, so Q = 40 ÷ 3.89022 = 10.2822 W for each metre.
Limits you should know
- Steady state only: the temperatures do not change with time. Heating up and cooling down (transient conduction) are not covered.
- One value of k for each layer. k changes with temperature, so use the value at the mean temperature of the layer.
- The temperatures are those of the surfaces. To start from the air temperature on each side, add the surface films in the Thermal Resistance Calculator.
- Layers are assumed to touch perfectly; a contact resistance can be added in the Thermal Resistance Calculator.
- For the heat lost by a hot pipe to the air, with convection and radiation from its surface, use the Steam Heat Loss Calculator. For the insulation thickness that meets a target, see the Insulation Thickness Calculator.
- The example conductivities are rounded values from common tables, not data for a product. This is arithmetic for learning and checking, not a design approval.