Work out how much heat is conducted through a solid layer by Fourier's law. Choose a flat wall, a pipe wall or pipe insulation, a spherical shell, or several layers in a row. You can find the heat flow, a face temperature, the thickness or the thermal conductivity.

Enter your values

Heat conducted through a flat layer: Q = k × A × (T1 − T2) ÷ L.

Your values

How well the material conducts heat. 0.04 W/(m·K) is an example for mineral wool. Use the value for your material, or fill in an example from the menu above.

The area the heat flows through, at right angles to the flow.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose the shape: a flat wall, a pipe (cylindrical layer), a spherical shell, or several layers in a row.
  2. Choose what you want to find: the heat flow, the temperature of one face, the thickness or the thermal conductivity k.
  3. Enter what you know. The temperatures are those of the two surfaces of the layer. You can fill in a rounded example conductivity from the menu.
  4. Choose Calculate. The result shows the heat flow, the heat flux, the thermal resistance and the working. Change the unit of a result with its menu.

The formulas (Fourier's law)

  • Flat wall: Q = k × A × (T1 − T2) ÷ L. The thermal resistance is R = L ÷ (k × A).
  • Pipe wall or pipe insulation: Q = 2π × k × ℓ × (T1 − T2) ÷ ln(r2 ÷ r1), with r1 the inner and r2 the outer radius and ℓ the length. R = ln(r2 ÷ r1) ÷ (2π × k × ℓ).
  • Spherical shell: Q = 4π × k × (T1 − T2) ÷ (1 ÷ r1 − 1 ÷ r2). R = (1 ÷ r1 − 1 ÷ r2) ÷ (4π × k).
  • Several layers: the resistances add up, R = R1 + R2 + …, and Q = (T1 − T2) ÷ R. The temperature falls by Q × R across each layer.
  • Heat flux is the heat flow for each square metre of area: q = Q ÷ A.

Worked examples

A flat layer of mineral wool 50 mm thick (k = 0.04 W/(m·K)) has an area of 10 m². One face is at 60 °C and the other at 20 °C. R = 0.05 ÷ (0.04 × 10) = 0.125 K/W, so Q = 40 ÷ 0.125 = 320 W, and the heat flux is 32 W/m².

The same insulation, 50 mm thick, around a pipe with an outside diameter of 60.3 mm, for 1 m of pipe: r1 = 0.03015 m and r2 = 0.08015 m. R = ln(0.08015 ÷ 0.03015) ÷ (2π × 0.04 × 1) = 3.89022 K/W, so Q = 40 ÷ 3.89022 = 10.2822 W for each metre.

Limits you should know

  • Steady state only: the temperatures do not change with time. Heating up and cooling down (transient conduction) are not covered.
  • One value of k for each layer. k changes with temperature, so use the value at the mean temperature of the layer.
  • The temperatures are those of the surfaces. To start from the air temperature on each side, add the surface films in the Thermal Resistance Calculator.
  • Layers are assumed to touch perfectly; a contact resistance can be added in the Thermal Resistance Calculator.
  • For the heat lost by a hot pipe to the air, with convection and radiation from its surface, use the Steam Heat Loss Calculator. For the insulation thickness that meets a target, see the Insulation Thickness Calculator.
  • The example conductivities are rounded values from common tables, not data for a product. This is arithmetic for learning and checking, not a design approval.