Works on this device
Heat Loss Calculator
Work out how much heat escapes through a wall, a window, a roof or a floor, how much energy that is over a time, and what it costs at your price. You can also compare a better U-value, find the standing loss of an insulated hot water tank, or measure the heat loss of a building from its energy use.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose what you want: the heat loss of one surface, the saving from a better U-value, the loss of an insulated tank, or the measured loss of a building.
- For a surface, choose whether you have a U-value or an R-value, in SI or US units, and type it with the area and the two temperatures.
- Type the time to get the energy lost. To see a cost, type your price for 1 kWh of heat. No price is built in; the example price is only for trying the tool.
- Choose Calculate. The result shows the heat loss in W, kW or BTU/h, the energy and the working.
The formulas
- Heat loss through a surface: Q = U × A × ΔT, with U = 1 ÷ R. ΔT is the inside temperature minus the outside temperature.
- Energy over a time: E = Q × t. 1 kWh = 3.6 MJ = 3,412.14 BTU.
- Cost: energy in kWh × your price for 1 kWh of heat.
- Tank: the side is a cylindrical layer, R = ln(r1 ÷ r0) ÷ (2π k H) + 1 ÷ (h × 2π r1 H); the top and bottom are flat layers, R = t ÷ (k A) + 1 ÷ (h A).
- Measured heat loss coefficient: heat given to the building ÷ (mean temperature difference × time), or ÷ (degree-days × 24 h).
Worked examples
A wall of 20 m² with a U-value of 0.3 W/(m²·K), 20 °C inside and 0 °C outside: Q = 0.3 × 20 × 20 = 120 W. In 24 hours that is 2.88 kWh; at a price of 0.12 for 1 kWh it costs 0.35.
Replacing a surface of U = 1.5 by U = 0.3 on the same 20 m² cuts the loss from 600 W to 120 W, by 80%. Over 24 hours that saves 11.52 kWh, or 1.38 at a price of 0.12.
A tank 450 mm across and 1,200 mm high, with 50 mm of insulation (k = 0.035 W/(m·K)), h = 8 W/(m²·K) outside, water at 60 °C and a room at 20 °C, loses 56.93 W: about 1.366 kWh a day.
A house used 450 kWh of gas for heating in 14 days, with a boiler efficiency of 90%, at a mean of 20 °C inside and 6 °C outside: 405 kWh ÷ (14 K × 336 h) = 86.1 W for each degree. At a difference of 23 K it loses about 1,980 W.
Limits you should know
- One surface at a time. For a whole room or house, with all walls, windows, roof and floor and the air that leaks in, use the BTU Calculator.
- The U-value must be that of the whole wall or window, with its surface films. To build it from layers, use the Thermal Resistance Calculator.
- For hot pipes, bare or insulated, use the Steam Heat Loss Calculator. For the insulation thickness that meets a target, see the Insulation Thickness Calculator.
- The temperature difference is taken as steady. Over a season, use the mean outside temperature of the season, or the measured choice with degree-days.
- A measured heat loss includes the heat from the sun, people and appliances only roughly; it is an estimate.
- This is arithmetic for planning and checking. It is not a heating design or a building regulation calculation.