Toolvito

Works on this device

Steam Heat Loss Calculator

Work out how much heat a steam or hot water pipe loses to the air around it, bare or with insulation, for each metre and for the whole run. For steam, the tool also gives the steam that condenses, and the loss over a year.

Enter your values

A bare pipe loses heat from its surface by convection and radiation. With steam, the tool also gives the steam that condenses.

Your values

Most steam gauges show gauge pressure, the pressure above the air. Choose absolute if your figure is from a steam table or a vacuum gauge.

The outside of the bare pipe. The menu above fills in the outside diameter of common steel pipe sizes.

From 0 to 1. Examples: about 0.8 to 0.95 for painted or rusty steel. Use the value for your surface.

8,760 for a pipe that is hot all year.

Your own cost of one tonne (1,000 kg) of steam, in the main unit of your money. No price is built in.

More options

Used only to turn a gauge pressure into an absolute pressure. 101.325 kPa is the standard atmosphere at sea level.

The walls and the ceiling that the pipe sees. Leave it empty to use the air temperature.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose a bare pipe or an insulated pipe.
  2. Choose steam at a pressure (gauge or absolute), or a fluid at a temperature you type, such as hot water.
  3. Enter the outside diameter of the pipe (the menu fills in common steel pipe sizes), its length and the air temperature. For insulation, type its thickness and its conductivity from the data sheet.
  4. Leave the convection on still air indoors, or type your own coefficient for wind or another case. Type the emissivity of the surface.
  5. Choose Calculate. To see a cost, type your own price; none is built in, and the example price is only for trying the tool.

How it is worked out

  • Steam temperature and latent heat come from IAPWS-IF97, the industrial formulation for water and steam: the saturation temperature at the absolute pressure, and hfg = h(steam) − h(water).
  • Convection: q = h × (Ts − Tair) for each m². In still air the tool uses h = 1.32 × (ΔT ÷ D)^0.25 W/(m²·K), the simplified equation for a horizontal pipe from Holman, Heat Transfer.
  • Radiation: q = ε × σ × (Ts⁴ − Tsur⁴), with σ = 5.670374 × 10⁻⁸ W/(m²·K⁴) and temperatures in kelvin.
  • Insulation: a cylindrical layer, R′ = ln(D2 ÷ D1) ÷ (2π × k) for each metre. The tool finds the outer surface temperature at which the heat through the insulation equals the heat that leaves the surface.
  • Steam condensed = heat loss ÷ hfg. Energy in a year = heat loss × hours.

Worked example

A bare steel pipe of NPS 4 (114.3 mm outside) carries steam at 7 bar gauge, in still air at 20 °C, with ε = 0.9. The absolute pressure is 801.325 kPa, so the steam is at 170.48 °C and hfg = 2,047.05 kJ/kg. The pipe loses 429.65 W/m by convection (h = 7.95 W/(m²·K)) and 574.48 W/m by radiation: 1,004.13 W/m in all. For 50 m that is 50.2 kW, and 88.29 kg of steam condenses every hour.

With 50 mm of insulation of k = 0.045 W/(m·K) and a jacket with ε = 0.9, the loss falls to 62.97 W/m, the jacket is at 30.49 °C, and the loss is cut by 93.7%.

Limits you should know

  • Steady state, a horizontal pipe in a large room. Wind outdoors, a vertical pipe or a pipe in a duct need a coefficient you type; the Convection Calculator can work one out.
  • The steam-side film and the steel wall are left out, so the loss is slightly high. Valves, flanges, supports and damaged insulation lose more and are not included.
  • Emissivity and conductivity are your figures; the examples are for trying the tool. For radiation between other surfaces, see the Thermal Radiation Calculator.
  • To find the insulation thickness that meets a surface temperature or a loss, see the Insulation Thickness Calculator. For the steam that a process uses, see the Steam Consumption Calculator; for flash steam and returned condensate, the Condensate Return Calculator.
  • Steam pressure up to 16.5 MPa (165 bar) absolute. This is an estimate for checking and planning, not a design approval; hot pipes can burn, and insulation design follows your standards.