Insulation Thickness Calculator
Work out how thick insulation must be to meet a goal: a surface temperature, a heat flow you allow, or a cold surface that stays dry above the dew point. It works for flat surfaces and pipes, for a target U-value of a wall or roof, and shows the critical radius of a small pipe.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose the kind of surface: a flat surface (a tank wall, a duct, an oven), a pipe, a wall or roof with a target U-value, or the critical radius of a small pipe or wire.
- For a flat surface or a pipe, choose the goal: a surface temperature, a heat flow you allow, or no condensation.
- Enter the temperatures, the conductivity k of the insulation from its data sheet, and the outer surface: its convection coefficient (or still air for a pipe) and its emissivity. The menu of examples fills in a whole case to try.
- Choose Calculate. The result shows the thickness, the surface temperature and the heat flow it gives, the working and, if you ask for it, the result for the next thickness your insulation is sold in.
How it is worked out
- The balance: the heat through the insulation equals the heat that leaves (or enters) its outer surface. Flat layer: k × (Tin − Ts) ÷ L. Pipe: 2π × k × (Tin − Ts) ÷ ln(D2 ÷ D1) for each metre. Surface: h × (Ts − Tair) + ε × σ × (Ts⁴ − Tsur⁴) for each m².
- Surface temperature goal: Ts is known, so a flat thickness follows at once, L = k × (Tin − Ts) ÷ q. For a pipe the tool searches for the outside diameter D2 that balances.
- Heat flow goal: the tool finds the thinnest layer that lets at most your heat flow through, solving the surface temperature for each thickness.
- No condensation: the dew point comes from the air temperature and relative humidity (Buck equation). The surface must stay at or above it, plus any margin you add.
- Still air on a pipe: h = 1.32 × (ΔT ÷ D)^0.25 W/(m²·K), the simplified equation for a horizontal cylinder from Holman, Heat Transfer. The pipe choice works a hot pipe out in the same way as the Steam Heat Loss Calculator.
- Target U-value: the R-values in series add up, so L = (1 ÷ U − R of the other layers) × k.
- Critical radius: r_cr = k ÷ h. On a pipe smaller than 2 × r_cr, a thin layer raises the heat flow.
Worked examples
A steam pipe at 170 °C with an outside diameter of 114.3 mm, in still air at 20 °C, with insulation of k = 0.045 W/(m·K) and a jacket of emissivity 0.9. For an outer surface of at most 45 °C it needs 18.5552 mm; the pipe then loses 125.700 W/m against 999.325 W/m bare. Rounded up to 20 mm, the surface is at 43.5522 °C and the loss is 119.146 W/m.
A chilled water pipe at 6 °C, 60.3 mm outside, in air at 30 °C and 80% relative humidity, with insulation of k = 0.036 W/(m·K): the dew point is 26.1687 °C, and 17.1277 mm keeps the surface at it. The pipe then gains 10.1412 W/m.
A roof should reach U = 0.25 W/(m²·K). Its other layers and surfaces give R = 0.5 m²·K/W, so the insulation must add 1 ÷ 0.25 − 0.5 = 3.5 m²·K/W. With k = 0.04 W/(m·K) that is 3.5 × 0.04 = 0.14 m, or 140 mm.
A wire 10 mm across with a sleeve of k = 0.2 W/(m·K) and h = 10 W/(m²·K): r_cr = 0.2 ÷ 10 = 20 mm. Up to 15 mm of sleeve the heat flow rises, by up to 67.6%; only beyond 247.176 mm is it lower than bare.
Limits you should know
- Steady state, one layer of one material with one k. Use the k at the mean temperature of the layer; it rises with temperature.
- The surface under the insulation is taken at the fluid or wall temperature you type. The steel wall and the film inside add a little resistance, so the thickness is on the safe side.
- Convection coefficients, emissivities and conductivities are your own figures; the examples are only for trying the tool. Wind outdoors needs a typed coefficient.
- For condensation, the insulation also needs a sealed vapour barrier. Joints, hangers and valves are where cold pipes sweat first. For the dew point on its own, see the Dew Point Calculator.
- The U-value choice is the plain layer method; studs, joists and fixings raise the real U-value. Building rules set their own targets and methods: the example target is not a current rule.
- For the heat lost by a pipe of a given thickness, see the Steam Heat Loss Calculator; for a wall, the Heat Loss Calculator; to add up layers, the Thermal Resistance Calculator and the Conduction Calculator.
- This is arithmetic for checking and planning. Insulation for hot surfaces, cold lines and fire protection follows the standards where you work; it is not a design approval.