Power Factor Correction Savings

Work out the capacitors that raise a power factor, and the money this saves. The saving depends fully on the rule in your electricity tariff, so you choose the rule and type its rates: none is built in.

Enter your values

The reactive power of the capacitors that raise the power factor, and the kVA and current before and after.

Your values

The kW of the load, from a meter or the bill. Use the kW at the time of the highest demand when the result is used for a demand charge.

From your bill or a power meter, as a number between 0 and 1.

The power factor you want to reach.

Installed, from your own quote. With it, the tool shows what the capacitor bank costs.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. To size the capacitors, choose Capacitor size (kvar). Type the real power in kW, the power factor now and the power factor you want.
  2. To find the saving, read your tariff sheet and choose the option that matches its rule for power factor.
  3. Type the rates from the tariff sheet, the bill periods in a year, and the cost of the correction if you want the payback time.
  4. Choose Calculate. Try an example fills the empty boxes with example values, so that you can see how an option works.

Which savings option fits your tariff

  • Demand is billed in kVA: the bill has a charge for each kVA of maximum demand.
  • Percentage penalty: the bill adds a percentage for each 0.01 of power factor below a set value, such as 0.90.
  • Billed demand is raised: demand is billed in kW, but multiplied by the set power factor ÷ your power factor when yours is lower.
  • Reactive energy is charged: the bill has a line for kvarh, often only for the part above a share of the kWh.
  • Energy is billed in kVAh: the energy price is for each kVAh, not for each kWh.
  • Lower losses: a small saving of energy in the cables and the transformer, with any tariff.
  • If your bill has none of these, a better power factor may save very little money.

The formulas

  • Power factor = real power (kW) ÷ apparent power (kVA) = cos φ.
  • Capacitor reactive power (kvar) = real power × (tan φ1 − tan φ2), with tan φ = √(1 − cos² φ) ÷ cos φ.
  • Apparent power (kVA) = real power ÷ power factor. The current falls in the same proportion.
  • Reactive energy (kvarh) = kWh × tan φ. kVAh = kWh ÷ power factor.
  • Losses in a conductor fall with the square of the current: loss after = loss now × (power factor now ÷ power factor after)².
  • Simple payback time = cost of the correction ÷ saving each year.

Worked example

A load of 200 kW has a power factor of 0.78. The apparent power is 200 ÷ 0.78 = 256.41 kVA. To reach 0.95, the capacitors must give 200 × (0.8023 − 0.3287) = 94.72 kvar. The apparent power falls to 210.53 kVA, and the current falls by 17.9%.

If the tariff charges 9.80 for each kVA each month, the demand charge falls by 45.88 kVA × 9.80 = 449.66 a month. Over 12 months it falls from 30,153.85 to 24,757.89, a saving of 5,395.96 a year.

If the tariff has a penalty of 1% of the bill for each 0.01 below 0.90, a power factor of 0.78 is 12 steps below, so the penalty is 12%. On an amount of 8,500 a month that is 1,020 a month, and 12,240 a year. At 0.95 there is no penalty.

Where to find your figures

  • Power factor now, kW, kVA, kWh and kvarh: your bill, the meter, or a power analyser.
  • The rule and the rates: the tariff sheet or the supply contract. The rules differ much between suppliers and countries.
  • Cost of the correction: a quote for the capacitor bank with its controller and fitting.
  • The values that Try an example fills in are for trying the tool. They are not current rates and not the rule of any real tariff.

Limits you should know

  • The real power is taken to stay the same. Capacitors do not lower the kWh that the load uses, apart from the small loss in the cables before them.
  • The power factor changes with the load. A demand charge depends on the power factor at the time of the highest demand, and kvarh and kVAh on the whole bill period. One average value is a simplification.
  • Only the one tariff rule you choose is counted. A reward for a high power factor, a minimum demand or a ratchet is not.
  • The kvar is for the load you type. A real bank comes in standard steps, and a changing load needs a bank that switches.
  • Harmonics from drives and other electronics can damage capacitors and need a bank made for them. The tool does not check this.
  • Each yearly cost is rounded to 2 decimal places, and a half is rounded away from zero. The saving is the difference of the two rounded costs.
  • The saving is an estimate from the figures you type. Fitting capacitors is electrical work for a qualified person. This page is not professional advice.