Electrical Power Calculator
Find electrical power from volts and amps, or find the amps or volts from the power. It covers DC, single-phase and three-phase, with power factor. It also shows kVA and kvar, the current of a motor, and the kilowatt-hours a load uses.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose what you want to calculate. Pick a Single-phase or Three-phase option that names the value you are missing.
- Enter the values you know. For three-phase, the voltage is the one between two line wires, and the current is the one in each line wire.
- Enter the power factor. Use 1 for heaters and other plain resistors. For a motor, read it from the nameplate.
- Choose Calculate. The result shows the working with your numbers. You can change the unit of a result.
The formulas
- DC or a plain resistor: P = V × I = I² × R = V² ÷ R.
- Single-phase AC: real power P = V × I × power factor. Apparent power S = V × I.
- Three-phase, balanced: P = √3 × V × I × power factor, with the line-to-line voltage and the line current. S = √3 × V × I. √3 is 1.732.
- Power triangle: S² = P² + Q². P is the real power in watts, Q the reactive power in var, S the apparent power in VA. Power factor = P ÷ S.
- Star and delta: in star the voltage across each load is the line voltage ÷ √3. In delta the line current is √3 × the current in each load.
- Energy: kilowatt-hours = kilowatts × hours.
Worked examples
Single-phase: 230 V and 12.5 A at a power factor of 0.8 give P = 230 × 12.5 × 0.8 = 2,300 W. The apparent power is 2,875 VA and the reactive power is 1,725 var.
Three-phase power: 400 V and 10 A at 0.8 give P = 1.732 × 400 × 10 × 0.8 = 5,543 W. The apparent power is 6.928 kVA and the line-to-neutral voltage is 230.9 V.
Three-phase current: a 15 kW load on 400 V at 0.85 draws I = 15,000 ÷ (1.732 × 400 × 0.85) = 25.47 A in each line.
Power triangle: 4 kW and 3 kvar give 5 kVA, a power factor of 0.8 and an angle of 36.87°.
Star and delta: three 23 Ω heater elements on 400 V take 10.04 A and 6,957 W in star. In delta they take 30.12 A in each line and 20,870 W, three times as much.
Motor: a three-phase motor with 7.5 kW at the shaft, 90% efficiency and a power factor of 0.85 on 400 V takes 7.5 ÷ 0.9 = 8.333 kW and 14.15 A.
Energy: a 1,500 W heater used 5 hours a day uses 7.5 kWh each day and 225 kWh in 30 days.
Unbalanced loads and the neutral
When the three lines of a four-wire star supply carry different currents, the page adds up the power of each line. It finds the neutral current as the sum of the three currents with their angles. With 10 A at power factor 1, 15 A at 0.9 and 20 A at 0.8 on 230 V, the total is 9,085 W and the neutral carries 11.43 A.
Limits you should know
- The result is arithmetic for understanding and estimating. It is not a design. Electrical work must follow your local code and be done or checked by a qualified electrician.
- It does not choose a wire size, a breaker, a fuse or a transformer, and it holds no table from any wiring code.
- Voltages and currents are RMS values of sine waves. Loads that draw current in pulses, such as many electronic power supplies, do not follow these formulas exactly.
- The three-phase formulas with √3 need a balanced load. Use the unbalanced option when the line currents differ.
- The power factor has no lead or lag sign here. The unbalanced option takes all three loads as lagging.
- The motor option gives the running current from the physics. Starting current is several times higher, and code tables for motor current are not built in.
- The three-phase voltages in the menu (208, 400, 415, 480, 600 and 690 V) are common nominal values, there to save typing. Use the voltage of your own supply.
- The energy option does not know your tariff. For money, use the Electricity Cost Calculator.