Power Factor Calculator

Find the power factor of a load from the readings you have, or the size of the capacitor that corrects it. Choose what you want to work out and enter your own figures.

Enter your values

Use this with a power meter reading in watts and a voltage and current reading.

Your values

The power in watts or kilowatts that the load uses, from a power meter.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose what you want to work out, for example Power factor from watts, volts and amps.
  2. Choose single-phase or three-phase where the form asks for it. For three-phase, enter the voltage between two lines.
  3. Enter the readings. The real power in kW comes from a power meter, not from volts times amps.
  4. Choose Calculate. The result shows the power factor, the phase angle and the real, reactive and apparent power.
  5. For a correction, enter the power factor now and the one you want. The result shows the capacitor reactive power in kvar and the capacitance.

The formulas

  • Power factor = real power ÷ apparent power = kW ÷ kVA. It is the cosine of the phase angle φ between voltage and current.
  • Power triangle: kVA² = kW² + kvar². Tan φ = kvar ÷ kW.
  • Apparent power, single-phase: VA = volts × amps.
  • Apparent power, three-phase: VA = √3 × line-to-line volts × amps. √3 is about 1.732.
  • From resistance and reactance: power factor = R ÷ square root of (R² + X²).
  • Correction: capacitor kvar = kW × (tan φ1 − tan φ2), where cos φ1 is the power factor now and cos φ2 the one wanted.
  • Capacitance, single-phase: C = Q ÷ (2π × f × V²), with Q in var, f in hertz, V in volts and C in farads.
  • Capacitance, three-phase: with three capacitors in delta, each is Q ÷ (3 × 2π × f × V²). In wye (star), each is Q ÷ (2π × f × V²). V is the line-to-line voltage and Q the total reactive power.

Worked example

A three-phase load uses 55 kW and draws 100 A at 400 V. Apparent power = 1.732 × 400 × 100 = 69.28 kVA. Power factor = 55 ÷ 69.28 = 0.7939. The reactive power is 42.13 kvar and the phase angle is 37.45°.

A load of 100 kW has a power factor of 0.75 and you want 0.95. Tan φ1 = 0.8819 and tan φ2 = 0.3287, so the capacitor reactive power is 100 × (0.8819 − 0.3287) = 55.32 kvar. At 400 V and 50 Hz with three capacitors in delta, each capacitor is 366.9 µF. The supply current falls from 192.45 A to 151.93 A.

With 80 kW and 100 kVA, the power factor is 0.8 and the reactive power is 60 kvar.

Limits you should know

  • This result is arithmetic for understanding and estimating. It is not a design. Electrical work must follow the local code and be done or checked by a qualified electrician.
  • The power triangle holds for sine-wave voltage and current. Loads with harmonics, such as drives, rectifiers and many power supplies, have a lower true power factor.
  • The readings do not show if the power factor is lagging or leading. The correction options take the load as lagging, as motors are.
  • Capacitors for power factor correction must be made and rated for that use. Harmonics can overload them and cause resonance. The tool does not choose a capacitor, a switching step or a protective device.
  • A penalty or a discount for power factor is a rule of your electricity tariff. It differs by utility and is not built in.
  • The three-phase formulas are for a balanced load with the same current in all three lines.