Find the current a motor draws at full load, the power from a measured current, or how heavily a motor is loaded. Choose what you want to work out and enter the figures from the nameplate and from your measurements.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose what you want to work out, for example Full-load current from the rated power.
- Choose three-phase, single-phase or DC. For three-phase, enter the voltage between two lines.
- Enter the rated power in kW, or choose hp for a motor rated in mechanical horsepower.
- Enter the efficiency and the power factor from the nameplate or the data sheet. The starting values are examples.
- Choose Calculate. You can copy the result, print it or download it as a CSV file.
The formulas
- Input power, three-phase: P = √3 × line-to-line voltage × current × power factor. √3 is about 1.732.
- Input power, single-phase: P = voltage × current × power factor. For DC: P = voltage × current.
- Full-load current = rated output ÷ (voltage × efficiency × power factor), with √3 in the bottom line for three-phase.
- Load from input power = measured input power ÷ (rated output ÷ efficiency at full load) × 100.
- Load from current (a rough estimate) = measured current ÷ nameplate current × measured voltage ÷ nameplate voltage × 100.
- Load from slip = (synchronous speed − measured speed) ÷ (synchronous speed − nameplate speed) × 100.
- Synchronous speed (rpm) = 120 × frequency ÷ number of poles.
- Torque: power (W) = torque (N·m) × angular speed (rad/s), so torque (N·m) = 9549.30 × kW ÷ rpm and torque (lb·ft) = 5252.11 × hp ÷ rpm.
- Horsepower: one mechanical horsepower is 745.699872 W. Motors made to IEC standards are rated in kilowatts.
Worked example
A three-phase motor is rated 15 kW at 400 V, with an efficiency of 91% and a power factor of 0.85. Input power = 15 ÷ 0.91 = 16.48 kW. Full-load current = 16,484 ÷ (1.732 × 400 × 0.85) = 27.99 A. In mechanical horsepower the output is 15,000 ÷ 745.7 = 20.12 hp.
You measure 400 V, 21 A and a power factor of 0.80 on this motor. Input power = 1.732 × 400 × 21 × 0.80 = 11.64 kW. Load = 11.64 ÷ 16.48 = 70.6% of the rated output.
At 50 Hz a 4-pole motor has a synchronous speed of 120 × 50 ÷ 4 = 1500 rpm. With 1460 rpm on the nameplate and 1475 rpm measured, the slip method gives (1500 − 1475) ÷ (1500 − 1460) = 62.5% load.
The torque of 15 kW at 1460 rpm is 9549.30 × 15 ÷ 1460 = 98.11 N·m.
Why there is no full-load current table
Electrical codes print tables of motor full-load current for sizing cables and protective devices. Those tables are official figures that differ by country and edition, so they are not built into this tool. Read the current on the nameplate of your motor. The calculated value here helps you understand and check it.
Limits you should know
- This result is arithmetic for understanding and estimating. It is not a design. Electrical work must follow the local code and be done or checked by a qualified electrician.
- Efficiency and power factor change with the load. The starting values are examples, not the data of your motor.
- The current method is rough, most of all below half load. The slip method depends on a nameplate speed that may be rounded.
- Starting current, no-load current, breaker, fuse and cable sizes are not worked out.
- The DC motor option is the simple model of a permanent-magnet motor. It leaves out friction and iron losses.
- The list of several motors adds power and current. The code rule for a supply to several motors is not built in.
- Stepper and servo motors are chosen from the inertia of the load and the torque curve of the maker. That is not covered.