Generator Sizing Calculator
Work out how big a generator must be for the loads you want to run at the same time. Type the running watts and the starting watts of each load from its nameplate. The page adds them up, adds your headroom, and shows the size in watts, kW and kVA.
Enter your values
Check these values
This is off unless you turn it on. Saved entries stay in this browser only. Untick the box to delete them.
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Replace the example rows with the loads you want to run at the same time. Enter how many, and the running watts of one, from the nameplate or the manual.
- For a load with a motor or a compressor, also enter its starting watts. Leave that box blank for lights, heaters and electronics.
- Choose how the loads start. One at a time is the usual rule of thumb. All at the same moment gives the larger, safe-side figure.
- Set the headroom in percent, and the power factor and voltage of the generator.
- Choose Calculate. Look for a generator whose running power and surge power are both at least the two figures shown.
The method
- Running watts = the sum of how many × running watts, for every load.
- Starting surge of a load = its starting watts − its running watts.
- Peak while starting, one at a time = total running watts + the largest single starting surge. This is a rule of thumb: it takes the motors to start one after another.
- Peak while starting, all together = the sum of how many × starting watts.
- With headroom = figure × (1 + headroom ÷ 100).
- kVA = kW ÷ power factor. Amps = VA ÷ volts, or VA ÷ (1.732 × line-to-line volts) for three-phase.
Worked example
The example rows are a refrigerator (200 W running, 1,200 W starting), a water pump (800 W running, 2,000 W starting), ten 10 W lights and a 1,000 W microwave oven. These are made-up numbers to show the method.
Running watts: 200 + 800 + 100 + 1,000 = 2,100 W. The surges are 1,000 W for the refrigerator and 1,200 W for the pump, so the largest is 1,200 W. Peak while starting: 2,100 + 1,200 = 3,300 W.
With 20% headroom: 2,100 × 1.2 = 2,520 W running and 3,300 × 1.2 = 3,960 W while starting. At a power factor of 0.8 the running power is 3.15 kVA, which is 13.7 A at 230 V single-phase.
If every load started at the same moment, the peak would be 4,300 W, or 5,160 W with headroom.
kW, kVA and motor starting
A generator rated 10 kVA at a power factor of 0.8 gives 8 kW. At 230 V single-phase that is 43.48 A. At 400 V three-phase it is 14.43 A in each line.
A motor draws its locked-rotor current (LRA on the nameplate) for a moment when it starts. On 230 V single-phase, an LRA of 60 A is 230 × 60 ÷ 1000 = 13.8 kVA, while a running current of 10 A is 2.3 kVA. How much of that a generator can take is in the data of its maker.
Fuel and running time
Read the fuel use of your generator in its data sheet, at the load you expect. With 3.5 litres an hour and a 25 litre tank, one tank lasts 25 ÷ 3.5 = 7.14 hours, and 24 hours need 84 litres. The page has no fuel figure of its own.
Limits you should know
- The result is arithmetic for understanding and estimating. It is not a design. Electrical work must follow your local code and be done or checked by a qualified electrician.
- A generator must be connected to the wiring of a building only through a proper transfer switch, fitted by a qualified person. This page gives no connection instructions.
- The example rows and example lists are made-up illustrations. Starting watts differ a lot from one motor to another: use the nameplate or the manual of each load.
- The rule of thumb with the largest single surge is a common convention, not a standard. For large motors, electronic loads, lifts or medical equipment, the maker of the generator must size it.
- The headroom is your choice. The power a generator can give also falls with altitude and heat: see the data of the maker.
- It does not size a generator from the floor area of a house or from kilowatt-hours on a bill. A generator is sized by the highest watts at one time.
- Run a generator outdoors only, away from doors and windows. Its exhaust holds carbon monoxide.