Works on this device

Electrical Load Calculator

List your loads with their ratings, and the page adds them up. It gives the connected load and the demand load in kW and kVA, and the current in each line of a single-phase, split-phase or three-phase supply. You type the demand factors yourself: no wiring code is built in.

Enter your values

A load schedule: the total kW and kVA, the demand load with the factors you type, and the current in each line.

Your values

For three-phase this is the line-to-line voltage ÷ 1.732: 230 V on a 400 V supply, 120 V on 208 V, 277 V on 480 V. For split-phase it is half the larger voltage: 120 V on 120/240 V.

Loads

One row for each load or group of equal loads, with the rating from its nameplate. The rows at the start are examples: replace them with your own. Demand factor: 100 counts the load in full; type the factor of your wiring code or of your own study.

This is off unless you turn it on. Saved entries stay in this browser only. Untick the box to delete them.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose the supply and enter the voltage from a line to neutral.
  2. Replace the example rows with your own loads. For each one enter how many there are, the rating from the nameplate and its unit: W, kW, VA, kVA or amps.
  3. Enter the power factor of the load. Use 1 for heaters and kettles. For motors and electronic loads, read it from the nameplate.
  4. Choose what each load is connected to. On a three-phase supply, spread the single-phase loads over the three lines.
  5. Leave the demand factor at 100% to count every load in full, or type the factor of your wiring code or of your own study.
  6. Choose Calculate. You can save the list on this device, or download it as a file.

What the page works out

  • Real power of a load in watts, and apparent power in volt-amperes: VA = W ÷ power factor. A rating in amps is multiplied by the voltage across the load.
  • Connected load: every load in full. Demand load: every load multiplied by its demand factor.
  • kVA totals come from the total kW and the total reactive power: kVA² = kW² + kvar².
  • Line currents: the currents of the loads are added with their angles. A load between two lines flows in both lines and not in the neutral. A balanced three-phase load takes a third of its power from each line.
  • Neutral current: the sum of the line currents with their angles. Equal loads on all lines cancel in the neutral.

Worked example

On a 230 V single-phase supply: ten 9 W lights at power factor 0.9, a 2 kW kettle, a 3 kW water heater, and an air conditioner of 6.5 A at power factor 0.9.

Real power: 90 + 2,000 + 3,000 + 6.5 × 230 × 0.9 = 6,435.5 W, so the connected load is 6.436 kW. The apparent power is 6.473 kVA and the current is 6,473 ÷ 230 = 28.14 A.

On a 120/240 V split-phase supply, 1,800 W on line 1 and 600 W on line 2 draw 15 A and 5 A. The neutral carries the difference, 10 A. A 4,800 W dryer across the two lines adds 20 A to each line and nothing to the neutral.

One circuit against its breaker

The second option adds up the amps of the loads on one circuit. A 900 W toaster, a 1,000 W coffee maker and two 0.5 A lamps on 120 V draw 7.5 + 8.33 + 1 = 16.83 A. If you allow 80% of a 20 A breaker, that is 16 A, and the page says Fail. The percent is yours to type: your wiring code sets it.

Demand, diversity and load factor

  • Demand factor = maximum demand ÷ connected load.
  • Diversity factor = sum of the maximum demands of the parts ÷ maximum demand of the whole. It is 1 or more.
  • Load factor = average load ÷ maximum demand over the same period.
  • With a connected load of 120 kW, a maximum demand of 78 kW, parts that add up to 96 kW and an average of 45 kW: demand factor 65%, diversity factor 1.231, load factor 57.69%.

Limits you should know

  • The result is arithmetic for understanding and estimating. It is not a design. Electrical work must follow your local code and be done or checked by a qualified electrician.
  • No method of a wiring code is built in: no load for each square metre or square foot, no demand factor table, no rule for the size of a service, a breaker or a cable. A dwelling or building load calculation that a code asks for must follow that code. Here you can only type its factors yourself.
  • The example rows and example lists are made-up loads to show the form. They are not typical values for a house or a workshop.
  • All loads are taken as lagging, on a supply whose line-to-neutral voltages are equal. Harmonic currents, which add in the neutral, are not counted.
  • A motor draws several times its running current while it starts. That is not part of a load list.
  • The saved list stays in this browser on this device.