Works on this device
Voltage Drop Calculator
Find how many volts are lost in a wire or cable run. Choose the circuit, the conductor size and material, and enter the current and the one-way length. The page shows the drop in volts and as a percent, the voltage left at the load, and the power lost in the wire.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose the circuit: DC, AC single-phase or AC three-phase. You can pick a common supply voltage from the menu, or type your own.
- Enter the load current and the one-way length of the run. The page counts the way back itself.
- Choose the conductor size in AWG, kcmil or mm², and copper or aluminium. Set the conductor temperature.
- Choose Calculate. To compare all sizes at once, choose Voltage drop table for every wire size.
The formulas
- DC and single-phase: voltage drop = 2 × I × R. R is the resistance of one wire over the one-way length. The 2 counts the way out and the way back.
- Three-phase, balanced: voltage drop = √3 × I × R, between two lines. √3 is 1.732.
- Resistance of a wire: R = resistivity × length ÷ cross-section. At 20 °C copper is 1 ÷ 58 = 0.017241 Ω·mm²/m and aluminium is 0.028264 Ω·mm²/m.
- Temperature: R at T = R at 20 °C × (1 + α × (T − 20)), with α = 0.00393 for copper and 0.00403 for aluminium, per °C.
- AWG sizes come from the formula of the gauge: diameter in inches = 0.005 × 92^((36 − n) ÷ 39).
- Power factor and reactance (under More options): the page solves supply voltage = load voltage + current × impedance with the angles counted. With power factor 1 and no reactance this is the same as the plain formula.
Worked example
A 120 V circuit feeds a 15 A load 30 m away through 12 AWG copper at 75 °C. The cross-section of 12 AWG is 3.309 mm². Resistance: 0.017241 × (1 + 0.00393 × 55) ÷ 3.309 = 6.337 Ω/km, so one wire of 30 m has 0.1901 Ω.
Voltage drop = 2 × 15 × 0.1901 = 5.70 V. That is 4.75% of 120 V. The load gets 114.3 V and the wire turns 85.6 W into heat.
With a limit of 3% (3.6 V), the longest run on 12 AWG is 18.9 m. In the table of sizes, 10 AWG is the first size within 3%: it drops 3.59 V over the 30 m.
Several loads along one run
When lights or alarm devices are fed one after another, each part of the run carries only the current of the loads after it. Three loads of 2 A each, 10 m apart on 12 AWG copper at 75 °C from 120 V, give 119.24 V, 118.73 V and 118.48 V. The quick check that puts all 6 A at the far end gives a drop of 2.28 V in place of 1.52 V.
A resistor in series
A resistor drops V = I × R. At 20 mA a 150 Ω resistor drops 3 V and turns 0.06 W into heat. To get 9 V for a 20 mA load from 12 V you need (12 − 9) ÷ 0.02 = 150 Ω. This works at one current only.
Limits you should know
- The result is arithmetic for understanding and estimating. It is not a design. Electrical work must follow your local code and be done or checked by a qualified electrician.
- No rule of a wiring code is built in. The page does not know the largest drop your code allows, and it does not check that a size may carry the current. The limit is the number you type. 3% and 5% are often quoted examples, not rules of this page.
- The resistance is the DC resistance of a solid conductor of the nominal cross-section. A stranded cable differs a little. You can type the resistance from the cable maker or from the table of your code in place of it.
- For large AC cables, skin effect and reactance add to the drop. Type the reactance from the cable data under More options. The table of sizes and the several-loads option count resistance only.
- The load is taken to draw the current you type, whatever voltage it gets. A motor that starts, or a load that draws more current at a lower voltage, behaves differently.
- It does not work out short-circuit current, or the voltage drop inside a transformer, a battery, a diode or an LED.
- The supply voltages in the menu are common nominal values, there to save typing.