Wire Resistance Calculator
Find the resistance of a copper or aluminium wire from its size and length, with a correction for temperature. For any other material, type the resistivity from the data sheet of the wire maker.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose what you want to work out, for example Resistance of a wire.
- Choose the material. For a material that is not copper or aluminium, choose the last option and type its resistivity.
- Give the size of the wire as an AWG size, a cross-section area, a diameter, or a number of strands with the strand diameter.
- Enter the length. Tick the box to count the way there and back, when the current goes out on one conductor and returns on another.
- Enter the temperature of the wire if it is not 20 °C, and choose Calculate.
The formulas
- Resistance: R = ρ × L ÷ A. ρ is the resistivity, L the length and A the cross-section area.
- Temperature: ρ at a temperature T = ρ at 20 °C × (1 + α × (T − 20 °C)). α is the temperature coefficient of resistance at 20 °C.
- Area of a round wire: A = π × diameter² ÷ 4. For a stranded wire: number of strands × area of one strand.
- AWG size: diameter in inches = 0.005 × 92 to the power of ((36 − n) ÷ 39), where n is the gauge number. For 1/0, 2/0, 3/0 and 4/0, n is 0, −1, −2 and −3.
- Length from resistance: L = R × A ÷ ρ. Resistivity: ρ = R × A ÷ L.
- Temperature from resistance: T2 = (R2 ÷ R1 × (1 + α × (T1 − 20 °C)) − 1) ÷ α + 20 °C.
Standard values used
For copper and aluminium the tool uses the standard values at 20 °C in the table. A real wire can differ a little with its purity and how it was drawn. For every other material, such as nichrome, Kanthal, steel or tungsten, the resistivity depends on the alloy and its maker, so you type it yourself.
| Material | Resistivity at 20 °C | Temperature coefficient at 20 °C | Standard |
|---|---|---|---|
| Copper (annealed) | 0.017241 Ω·mm²/m (1/58) | 0.00393 per °C | IEC 60028, the International Annealed Copper Standard |
| Aluminium (hard-drawn) | 0.028264 Ω·mm²/m | 0.00403 per °C | IEC 60889 |
Worked example
A copper wire of size 12 AWG is 100 m long at 20 °C. Its diameter is 0.005 × 92 to the power of (24 ÷ 39) = 0.0808 in, which is 2.053 mm, so its area is 3.309 mm². Resistance = 0.017241 × 100 ÷ 3.309 = 0.5211 Ω. That is 5.211 Ω for one kilometre and 1.588 Ω for 1000 feet.
With the box for the way there and back ticked, the length counted is 200 m and the resistance is 1.042 Ω.
A copper winding measures 10 Ω at 20 °C. At 75 °C its resistance is 10 × (1 + 0.00393 × 55) = 12.16 Ω.
Limits you should know
- This result is arithmetic for understanding and estimating. It is not a design. Electrical work must follow the local code and be done or checked by a qualified electrician.
- Skin effect is left out: the result is the resistance for direct current. For alternating current in thick conductors, or at a high frequency, the resistance is higher. This also holds for litz wire, which is made to lower that effect.
- AWG sizes are taken as solid round wire. A stranded cable of the same AWG, and a real metric cable of a nominal size, can have a slightly different resistance.
- The straight-line temperature rule is a good fit near room temperature and less exact far from it. It is not a model for heating wire at its working temperature unless you type the values for that temperature.
- The tool does not say how much current a wire may carry or which size to install. The allowed current is set by the electrical code of your country.
- No data of alloys or wire makers is built in.