Wire Current Capacity Calculator
The current a wire may carry is set by the electrical code of your country, not by a formula. This tool does the arithmetic on the values you read from your own code: the table value, the correction factors and your load.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
Why this page shows no current capacity chart
The allowed current of a wire (its ampacity, or current-carrying capacity) comes from tables in electrical codes, such as the National Electrical Code in the United States or the IEC 60364 series used in many other countries. The value for one wire size is not one number. It changes with the country and the edition of the code, the conductor material, the temperature rating of the insulation, the ambient temperature, how many cables run together, and whether the cable is in air, in a conduit, in a wall or in the ground. The tables are also revised.
A chart on a web page cannot know which of these applies to you, and a wrong value can start a fire. So this tool holds no chart and never says that a wire is safe for a current. You read the values from your own code, and the tool does the arithmetic and shows the working.
How to use this calculator
- In the table of your electrical code, find the allowed current for your conductor size, material, insulation and way of installing. Type it into the first field.
- From the same code, type the correction factor for the ambient temperature and the one for grouping. Type 1 where the code says that no correction applies.
- Enter your load current and the continuous-load factor of your code in per cent. Enter 100 if your code has none.
- Choose Calculate. The result shows the corrected allowed current, your load as counted, and which of the two numbers is larger.
- To go the other way, choose Smallest table value to look for, from your load. Then find the first size in your table that has at least that value.
The arithmetic
- Corrected allowed current = table value × correction factor for temperature × correction factor for grouping × any other factor.
- Load current counted = load current × continuous-load factor ÷ 100.
- Smallest table value to look for = load current counted ÷ the correction factors.
- Heat in a wire (the physics option) = current² × resistance of one metre, in watts for each metre.
Worked example
The numbers in this example and in the Try an example button are for trying the tool. They are not current rules and they are not values for your wire.
Say your table gives 30 A, the temperature factor is 0.88 and the grouping factor is 0.8. Corrected allowed current = 30 × 0.88 × 0.8 = 21.12 A. A load of 16 A with a continuous-load factor of 125% counts as 20 A. That is 94.7% of the corrected value, and 20 A is not above 21.12 A.
The other way: for the same load and factors, the smallest table value to look for is 20 ÷ (0.88 × 0.8) = 28.41 A.
The physics option: a copper conductor of size 12 AWG at 20 °C has 5.211 mΩ for each metre. At 16 A it makes 16² × 0.005211 = 1.334 W of heat for each metre. This number explains why a wire warms up; it is not a limit.
Limits you should know
- This result is arithmetic for understanding and estimating. It is not a design. Electrical work must follow the local code and be done or checked by a qualified electrician.
- The tool has no table of allowed current and no correction factors of any code. Every such value is your input, and the result is only as right as those inputs.
- The comparison does not say that a wire is suitable. A code also has rules for the fuse or breaker, the temperature rating of the terminals, the voltage drop and the fault current.
- The correction factors of a code can depend on the wire size and the insulation, so check them again when you change the size.
- The heat option is physics only. It cannot give an allowed current, because that depends on how the heat leaves the wire.
- Printed circuit board traces follow other rules and are not covered here.