Toolvito

Works on this device

Wire Gauge Calculator

Find the smallest wire size that keeps the voltage drop of a run within the limit you set. Then check that size against the current table of your own wiring code. The page also converts AWG sizes to millimetres, mm² and kcmil, reads SWG sizes, and adds up several wires into one size.

Enter your values

Finds the smallest standard size that keeps the voltage drop within your limit. Then you check that size against the current table of your wiring code.

Your values

The distance from the supply to the load. The page counts the way back itself.

Your wiring code or the maker of the equipment sets or recommends this limit. 3% and 5% are often quoted examples, not rules built into this page.

A warm conductor has more resistance. 20 °C is a cold wire. 60 to 90 °C are common limits of insulation for a wire at full load.

Leave 0 first. If your code table does not allow the current on the size found, type 1 to check the next larger size.

Calculate once to see the size. Then look up that size in the current-carrying capacity (ampacity) table of the wiring code that applies to you, for your insulation, temperature and way of installing, and type the value here. The example value is not a rule.

More options

Leave 1 for one conductor in each wire.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose the button below them.

How to find a wire size

  1. Choose Wire size for a load and a run. Choose the circuit, enter the supply voltage, the load current (or its power in watts) and the one-way length.
  2. Type the largest voltage drop you accept, as a percent. Your code or the maker of the equipment sets it. Then choose AWG or metric sizes, the material and the conductor temperature.
  3. Choose Calculate. The result names the smallest listed size within your limit.
  4. Look up that size in the current-carrying capacity table of the wiring code that applies to you, and type the allowed current. Calculate again: the page says Pass or Fail.
  5. On a fail, type 1 in Go up by this many sizes, look up the larger size, and try again.

Why the page asks you for the allowed current

Two things decide a wire size. The first is voltage drop, which is physics: this page works it out from the resistance of the wire. The second is the current the wire may carry without getting too hot. That is set by wiring codes, such as the National Electrical Code in the United States, the IEC 60364 series and national wiring rules. The value differs by country and edition, by insulation, by the temperature around the cable and by the way it is installed.

This page has no such table, on purpose. A size that passes on voltage drop can still be too small for the current, mostly on short runs. So the size is not finished until you have checked it in your own code table.

The AWG formula

American Wire Gauge sizes follow one formula: diameter in inches = 0.005 × 92^((36 − n) ÷ 39), where n is the gauge number. For 1/0, 2/0, 3/0 and 4/0, n is 0, −1, −2 and −3. A larger number is a thinner wire. Six gauge steps halve the diameter, and three steps halve the cross-section, almost exactly.

Sizes above 4/0 are given in kcmil, thousands of circular mils. One circular mil is the area of a circle one thousandth of an inch across, so 1 kcmil is 0.5067 mm².

Some AWG sizes from the formula
AWG Diameter (mm) Diameter (in) Cross-section (mm²)
4/0 11.684 0.4600 107.2
1/0 8.251 0.3249 53.48
6 4.115 0.1620 13.30
10 2.588 0.1019 5.261
12 2.053 0.0808 3.309
14 1.628 0.0641 2.081
18 1.024 0.0403 0.8230
24 0.5106 0.0201 0.2047

Worked example

A 120 V circuit feeds a 15 A load 30 m away, with copper at 75 °C and a limit of 3%. The allowed drop is 3.6 V. 12 AWG would drop 5.70 V (4.75%), which is too much. 10 AWG drops 3.59 V (2.99%), so 10 AWG is the smallest listed size within the limit.

You then look up 10 AWG in your code table. If the table allows 30 A for your insulation and installation, you type 30 and the page says Pass, because 30 A is not below 15 A.

14 AWG has a diameter of 1.628 mm and a cross-section of 2.081 mm². A 2.5 mm² wire has gauge number 13.21 by the formula, so the nearest AWG size is 13 AWG. Two 14 AWG wires side by side have 4.162 mm², the same as one 11 AWG.

Limits you should know

  • The result is arithmetic for understanding and estimating. It is not a design. Electrical work must follow your local code and be done or checked by a qualified electrician.
  • No current rating (ampacity), no voltage drop limit and no fuse or breaker rule of any wiring code is built in. The pass or fail compares the load current with the number you typed.
  • The size from voltage drop counts resistance only, for one load at the end of the run. For power factor, reactance or several loads along a run, use the Voltage Drop Calculator.
  • Resistance is the DC resistance of a solid conductor of the nominal cross-section, from the resistivity of copper (1 ÷ 58 Ω·mm²/m) or aluminium (0.028264 Ω·mm²/m) at 20 °C, corrected for temperature. A real cable differs a little.
  • Diameters are for one solid round wire. A stranded wire of the same gauge is wider overall.
  • SWG sizes come from a fixed table (Imperial Standard Wire Gauge). The list of metric sizes is the standard series from 0.5 to 630 mm².
  • It does not size speaker cable, heating wire (nichrome, Kanthal) or transformer windings.