Estimate how long a UPS carries a load on battery, how much battery a wanted runtime needs, or what size of UPS your equipment needs. The result is a simple energy estimate; the runtime chart of the maker takes precedence.

Enter your values

An estimate of how long a UPS carries a load, from the battery energy, the load, the efficiency and the usable share.

Your values

Example value. The data sheet of the UPS gives the efficiency on battery.

Example value. At the high current of a UPS, a lead-acid battery gives much less than its rated capacity.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose what you want to work out, for example Runtime of a UPS on battery.
  2. Enter the battery: the volts and amp-hours of one battery and the number of batteries, or the total watt-hours.
  3. Enter the load in watts. If you only know volt-amps (VA), choose that and enter the power factor of the load.
  4. Set the inverter efficiency and the usable share of the battery energy. The starting values are examples; use the figures of your UPS if you have them.
  5. Choose Calculate. The table shows the runtime at other loads by the same model.

The formulas

  • Battery energy (Wh) = volts × amp-hours × number of batteries.
  • Runtime (hours) = battery energy × usable share × inverter efficiency ÷ load in watts.
  • Battery needed (Wh) = load in watts × runtime in hours ÷ inverter efficiency ÷ usable share.
  • Watts and volt-amps: watts = volt-amps × power factor. A UPS has a rating for both, and the load must be within both.
  • Several devices: total VA = square root of (total watts² + total var²), where the var of a device = watts × tan φ and cos φ is its power factor.

Worked example

A UPS has two batteries of 12 V and 9 Ah. Battery energy = 12 × 9 × 2 = 216 Wh. With a usable share of 60% and an inverter efficiency of 90%, 216 × 0.6 × 0.9 = 116.64 Wh reach the load. A load of 300 W runs for 116.64 ÷ 300 = 0.389 hours, which is 23.3 minutes.

For 30 minutes at 300 W with the same figures, the battery energy needed is 300 × 0.5 ÷ 0.9 ÷ 0.6 = 277.8 Wh. At 24 V that is 11.57 Ah, so two strings of two 12 V 9 Ah batteries: four batteries.

A UPS rated 1500 VA and 900 W has an output power factor of 0.6. A load of 300 W uses 33.3% of its watt rating.

Why the real runtime differs

A battery does not give the same energy at every load. At the high current of a UPS, a lead-acid battery gives much less than its rated amp-hours, which are measured over 10 or 20 hours. At a low load, the power that the UPS itself uses becomes a large share. Age and temperature lower the capacity too.

For these reasons the runtime charts of UPS makers are curves, not straight lines, and they take precedence over this estimate. The usable share on this page is the way to bring the simple model close to a chart: set it so that one point of the chart is matched.

Limits you should know

  • This result is arithmetic for understanding and estimating. It is not a design. Electrical work must follow the local code and be done or checked by a qualified electrician.
  • The model is linear. It has no runtime chart and no battery data of any UPS maker or model.
  • The inverter efficiency, the usable share and the headroom are your inputs. The starting values are examples.
  • The battery option counts energy only. Use only the battery type, string voltage and battery size that the maker of the UPS allows.
  • Starting surges of motors, compressors and laser printers are not counted in the size option.
  • The three-phase input and output of large UPS systems, bypass and redundancy are not covered.