Transformer Calculator

Find the current of a transformer from its kVA rating, the kVA that a load needs, or the voltages and turns of an ideal transformer. Choose what you want to work out and enter your own figures.

Enter your values

The current on each side of a transformer when it carries its full rating.

Your values

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose what you want to work out, for example Full-load current from the kVA rating.
  2. Choose single-phase or three-phase where the form asks for it. For three-phase, enter the voltage between two lines.
  3. Enter the values from the nameplate or from your measurements, and pick a unit for each one.
  4. Some fields start empty, such as the per-cent impedance. Read these from the nameplate or the test report. Try an example fills them with example values.
  5. Choose Calculate. You can copy the result, print it or download it as a CSV file.

The formulas

  • Ideal transformer: primary voltage ÷ secondary voltage = primary turns ÷ secondary turns = secondary current ÷ primary current. The impedance ratio is the turns ratio squared.
  • Full-load current, single-phase: amps = kVA × 1000 ÷ volts.
  • Full-load current, three-phase: amps = kVA × 1000 ÷ (√3 × line-to-line volts). √3 is about 1.732.
  • kVA from a load: kVA = volts × amps ÷ 1000 (× √3 for three-phase), or kVA = kW ÷ power factor.
  • Efficiency = output ÷ (output + core loss + copper loss). The copper loss changes with the square of the load. The result has a table and a chart of the efficiency from 10% to 120% load.
  • Voltage regulation = (no-load voltage − full-load voltage) ÷ full-load voltage × 100.
  • Short-circuit current at the secondary terminals = full-load current × 100 ÷ per-cent impedance, for a supply with no impedance of its own.
  • Buck-boost: output = supply × (1 + low winding voltage ÷ high winding voltage) to boost, and supply ÷ the same factor to buck.
  • EMF equation: E = 4.44 × f × N × B × A for a sine wave. E is the RMS voltage, f the frequency, N the turns, B the peak flux density and A the core area.

Worked example

A three-phase transformer of 75 kVA has 480 V on the primary and 208 V on the secondary. Primary full-load current = 75,000 ÷ (1.732 × 480) = 90.21 A. Secondary full-load current = 75,000 ÷ (1.732 × 208) = 208.18 A.

With a per-cent impedance of 5.75%, the simple formula gives a short-circuit current at the secondary terminals of 208.18 × 100 ÷ 5.75 = 3620.5 A.

An ideal transformer with 1000 primary turns and 100 secondary turns has a turns ratio of 10. With 240 V on the primary, the secondary gives 24 V.

A buck-boost transformer with a 240 V primary winding and a 32 V secondary winding, connected to boost a 208 V supply, gives 208 × (1 + 32 ÷ 240) = 235.73 V. For a 40 A load its smallest rating is 40 × 32 ÷ 1000 = 1.28 kVA.

Why there are no fuse, breaker or cable sizes

The size of a fuse, a breaker or a cable for a transformer is set by the electrical code of each country, for example as a per cent of the full-load current that depends on the voltage, the impedance and the kind of protection. These rules differ from place to place and are revised. This tool does not build them in. It gives the full-load current that the rules start from.

The table of full-load current is worked out from the formula for the voltages you enter. It is not a table from a code or from a maker.

Limits you should know

  • This result is arithmetic for understanding and estimating. It is not a design. Electrical work must follow the local code and be done or checked by a qualified electrician.
  • The voltage, current and turns options use the ideal transformer: no losses, no leakage and no magnetizing current.
  • The short-circuit formula assumes an unlimited supply and a fault at the terminals. It leaves out the supply impedance, cables and the current that running motors add.
  • Per-cent impedance, losses and flux density are your inputs. The example values are for trying the tool; they are not the data of your transformer.
  • The buck-boost option is for one single-phase unit. Three-phase arrangements and the connection diagrams of makers are not covered.
  • The EMF equation options give turns, core area or flux density only. They do not choose wire, check the winding window or work out losses and heating. Flyback transformers are not covered.
  • Inrush current, magnetizing current, K-factor and the sizing of control transformers and current transformers are not worked out.