Works on this device
Hot Water Demand Calculator
Work out how much hot water a home or a building uses. Add a row for each shower, tap and machine, and get the hot water each day, in the busiest hour and at the peak flow, with the energy to heat it.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose Hot water each day and in the busiest hour, from fixtures.
- Add a row for each fixture or use: its flow, the minutes of each use, how many uses each day and how many in the busiest hour. Tick the fixtures that can run at the same time at the peak.
- Type the temperature you want at the tap, the temperature of the hot water and the temperature of the cold water supply. A row for a machine that takes the hot water as it is can have its own temperature.
- Choose Calculate. You get the hot water each day and in the busiest hour, the peak flow, the energy to heat the water, and a table for each fixture.
- To find only the hot share of a shower or a bath, choose Mix hot and cold water to a temperature.
The formulas
- Water each use = flow × minutes.
- Hot share = (temperature at the tap − cold) ÷ (hot − cold). It comes from the energy balance of mixing.
- Hot water each day = Σ water each use × hot share × uses each day. In the busiest hour: the same with the uses in that hour.
- Peak flow = the sum of the flows of the fixtures that run at the same time; the hot water flow is each flow × its hot share.
- Energy = hot water × density × specific heat × (hot − cold).
Worked example
Hot water at 120 °F is mixed with cold water at 50 °F to 105 °F at the tap. The hot share is (105 − 50) ÷ (120 − 50) = 78.6%.
Three showers a day of 8 minutes at 2 gpm use 48 gallons of mixed water, of which 37.7 gallons are hot. With a basin, a kitchen sink and a dishwasher as in the starting rows, the home uses 64.1 gallons of hot water a day and 31.0 gallons in the busiest hour.
The shower and the kitchen sink can run together: 3.5 gpm at the taps, of which 2.75 gpm is hot.
Limits you should know
- The flows, minutes and uses in the starting rows are examples. Use your own, or the figures of the design guide or plumbing code that applies to you. No table of any standard is built in.
- Pipes and tanks lose heat, so the real hot water use is a little higher, and the energy to heat it higher again.
- The cold water temperature changes with the season. For a design, take the coldest month.
- To size a tank or a tankless water heater for this demand, use the Water Heater Size Calculator. For the cost of heating the water, use the Water Heating Savings Calculator.
- This is an estimate, not a design. The hot water demand of a real building is set by a professional by the method used where you live.