Water Heater Size Calculator
Find what size of water heater meets your hot water demand. For a tank heater, work out its first-hour delivery from the tank, the burner or element and the temperature rise; for a tankless heater, the power for your flow.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Work out your hot water demand first: the hot water in the busiest hour for a tank, or the flow of the taps that run together for a tankless heater. The Hot Water Demand Calculator does this from your fixtures.
- For a tank heater you have in mind, choose First-hour delivery. Type the tank size, the input power, the recovery efficiency and the two water temperatures. Add your peak-hour demand to check it.
- To size a tank, choose Tank size or heater power for a peak demand, and find the tank for a heater power or the power for a tank.
- For a tankless heater, choose Tankless, and find the power for a flow or the flow for a power.
- Choose Calculate. You get the results and the working.
The formulas
- Temperature rise = hot water temperature − cold water temperature.
- Recovery rate = input power × recovery efficiency ÷ (density × specific heat × rise). In US units, about BTU/h × efficiency ÷ (8.34 × °F) gallons per hour.
- First-hour delivery = tank size × usable share + recovery rate × 1 hour.
- Tank for a peak = (demand − recovery × length of the peak) ÷ usable share. Power for a peak = (demand − tank × usable share) × density × specific heat × rise ÷ length of the peak ÷ efficiency.
- Tankless power = flow × density × specific heat × rise ÷ efficiency. In US units, about 500 × gpm × °F rise in BTU/h.
Worked example
A 50 gallon gas tank has a 40,000 BTU/h burner with a recovery efficiency of 78%. Cold water at 50 °F is heated to 120 °F, a rise of 70 °F. The recovery rate is 40,000 × 0.78 ÷ (8.34 × 70) = about 53.4 gallons per hour.
With 70% of the tank usable, the first-hour delivery is 50 × 0.7 + 53.4 = 88.4 gallons, enough for a peak hour of 60 gallons.
A tankless heater for 4 gpm at the same 70 °F rise must put 140,176 BTU/h into the water, so at 95% efficiency it needs an input of 147,554 BTU/h (43.2 kW).
Limits you should know
- The usable share, the recovery efficiency and the starting figures are examples. Use the maker's data for the heater you have in mind.
- The first-hour rating on a label comes from a standard test, not from this formula. When you have it, compare it with your peak-hour demand.
- Use the coldest inlet temperature of the year. In winter the rise is larger, and a heater gives less hot water.
- An electric tankless heater draws a large current. Its wires and breaker follow the maker's instructions and the electrical code.
- For the running cost, or the energy and time to heat a tank of water, use the Water Heating Savings Calculator.
- This is an estimate from your figures, not a design. The size of a water heater for a real building is set by the maker's data and the plumbing code or design method used where you live. This is not professional advice.