Thermocouple Voltage Calculator

A thermocouple gives a small voltage that depends on the temperature difference between its two junctions. This calculator turns a temperature into the voltage at the meter and a measured voltage back into a temperature, with cold-junction compensation. It holds no thermocouple tables: you give the slope, or the coefficients from the NIST tables.

Enter your values

A quick estimate: the voltage grows by a fixed amount for each degree between the two junctions.

Your values

About 41 µV/°C suits type K near room temperature. Choose an example or type the mean slope of your type over your range, from its table.

The tip of the thermocouple, where it touches what you measure.

Where the thermocouple wires join the copper of the meter or board. 0 °C for an ice bath.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

What this calculator does, and what it does not

The NIST ITS-90 reference functions of the thermocouple types are long polynomials with up to ten or more coefficients for each range. This tool does not carry them. It offers a linear estimate with a Seebeck coefficient (a slope) that you type or pick from rough examples, and exact work with the coefficients you type from the NIST tables or from the table of your sensor, in both directions.

How to use this calculator

  1. Choose the way: a constant Seebeck coefficient (a quick estimate), the reference function with coefficients you type, or an inverse function with coefficients you type.
  2. Choose whether you want the voltage for a temperature or the temperature for a measured voltage.
  3. Enter the temperature of the reference (cold) junction: where the thermocouple wires meet the copper of the meter or board. Use 0 °C for an ice bath.
  4. For the polynomial options, copy the coefficients for your type and range from the NIST ITS-90 Thermocouple Database, separated by commas, with E in mV and t in °C.

The formulas

  • Cold-junction compensation: the meter reads E(t) − E(t ref). So E(t) = measured voltage + E(t ref); then turn E(t) into a temperature.
  • Linear estimate: E(t) = S × t, with S the Seebeck coefficient in µV/°C. Then t = t ref + measured voltage ÷ S.
  • Reference function (NIST form): E = c0 + c1 t + c2 t² + ... , with t in °C and E in mV. Type K above 0 °C adds a0 × exp(a1 × (t − a2)²). The tool finds t for a voltage by halving the range until E(t) matches.
  • Inverse function (NIST form): t = d0 + d1 E + d2 E² + ... , with E in mV. This is the "voltage to temperature equation" of each type, for example type J or type T; each set of coefficients holds over its own range only.

Worked examples

Linear, type K at about 41 µV/°C: a junction at 200 °C with the reference at 25 °C gives 41 × (200 − 25) = 7,175 µV = 7.175 mV at the meter. Back: 7.175 mV + 41 × 25 µV = 8.2 mV, and 8.2 mV ÷ 41 µV/°C = 200 °C.

Reference function, with the made-up coefficients 0, 0.0395 and 0.000025 (E in mV): E(200 °C) = 7.9 + 1.0 = 8.9 mV and E(25 °C) = 1.003 mV, so the meter reads 7.897 mV.

Inverse function, with the made-up coefficients 0, 25 and −0.2: 7.175 mV measured plus 1 mV for the reference junction is 8.175 mV, and t = 25 × 8.175 − 0.2 × 8.175² = 191.01 °C.

The made-up coefficients only show the arithmetic; they are not those of any thermocouple type.

Limits you should know

  • A thermocouple is not linear. The linear estimate is close only near the range its slope was taken from; the example slopes are rough mean values from 0 °C to 100 °C.
  • Accurate work needs the NIST ITS-90 tables or functions of your type (NIST Monograph 175), or the table of your sensor. The result is only as good as the coefficients you type.
  • Real thermocouples have a tolerance class, and the wires, connectors and the meter add errors. The temperature of the reference junction must be measured well.
  • For a platinum resistance thermometer, use the Rtd Resistance Calculator.