Concrete Curing Maturity Calculator
The maturity method tracks how far concrete has cured from its temperature over time. Paste or type the readings of a temperature logger to get the Nurse-Saul temperature–time factor and the equivalent age, or work out how long curing takes at a temperature.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose Maturity from a temperature record, then type the readings (hours since placing and the concrete temperature), or paste them from your logger, one reading on each line.
- Type the datum temperature T0 and the activation energy E for your mix. These boxes start empty, because they come from tests of your mix (ASTM C1074). Try an example fills in example values.
- Keep or change the reference temperature Ts. Use the one your strength–maturity relation was made with.
- Choose Calculate. The table shows each interval and the chart compares the equivalent age with the real age.
- For a steady temperature, or the curing time needed at a temperature, choose the other calculations.
The formulas (ASTM C1074)
- Temperature–time factor (Nurse-Saul): M = Σ (Ta − T0) Δt, where Ta is the mean temperature in an interval Δt. An interval at or below T0 counts 0.
- Equivalent age (Arrhenius): te = Σ exp(−(E ÷ R)(1 ÷ Ta − 1 ÷ Ts)) Δt, with temperatures in kelvin and R = 8.314 J/(mol·K).
- Equivalent age (Nurse-Saul form): te = Σ (Ta − T0) ÷ (Ts − T0) Δt.
- Curing time at a steady temperature T: t = te ÷ exp(−(E ÷ R)(1 ÷ T − 1 ÷ Ts)), or t = M ÷ (T − T0) for a target factor.
Worked examples
The starting record on this page (20, 30, 34, 28, 24, 20 and 18 °C at 0, 12, 24, 48, 72, 120 and 168 hours) with an example datum of 0 °C gives M = 25 × 12 + 32 × 12 + 31 × 24 + 26 × 24 + 22 × 48 + 19 × 48 = 4,020 °C·h. At Ts = 20 °C that is an equivalent age of 201 h by the Nurse-Saul form, and 214.5 h by the Arrhenius form with an example E = 40 kJ/mol.
Concrete kept at 10 °C for 7 days (168 h) has M = 1,680 °C·h and, with E = 40 kJ/mol, an equivalent age of 94.1 h at 20 °C. To reach 7 days at 20 °C it needs 12.5 days at 10 °C (14 days by the Nurse-Saul form). The example datum and activation energy are not values for your concrete.
Limits you should know
- Maturity tells you strength only through a strength–maturity relation made in the laboratory for the same mix. Use the Concrete Strength Estimator with your relation.
- The datum temperature and the activation energy depend on the cement, the additions and the admixtures. The tool holds none; the examples are not values for your concrete.
- Each interval uses the mean of its two readings. Gaps in the record, and readings far apart, make the result less sure.
- The tool does not decide when forms may come off or loads may be applied. Your specification and tests do. It is not professional advice.