Heat Pump Sizing Calculator
Work out what size of heat pump a house needs. Start from the heat loss at the coldest design temperature, then check the balance point and the backup heat with the capacity data of the heat pump you are looking at.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Work out the heat loss of the house first. The BTU Calculator does this from the walls, windows and air leaks.
- Choose Heat pump size from the heat loss and type it. If it was worked out for another outdoor temperature, choose to scale it and type the temperatures.
- Choose Balance point and backup heat and type the heating capacity of the heat pump at two or more outdoor temperatures from the maker's table. The tool finds where the heat pump stops covering the heat loss and how much backup heat is needed at the design temperature.
- For a ground-source or water-source heat pump, choose tonnage from the loads.
- Choose Calculate. You get the results, the working and, for the balance point, a chart and a table.
The formulas
- Capacity needed = heat loss at the outdoor design temperature × (1 + extra for safety ÷ 100).
- Scaling a heat loss: heat loss at the design temperature = known heat loss × (inside − design temperature) ÷ (inside − outdoor temperature of the known figure).
- Heat loss line: the heat loss at the design temperature, falling in a straight line to zero at the outdoor temperature with no heat needed.
- Capacity line: straight lines between the points of the maker's data.
- Balance point: where the two lines cross. Backup heat at the design temperature = heat loss − heat pump capacity.
- Tons = BTU/h ÷ 12,000. Ground loop: heat taken from the ground = heating load × (1 − 1 ÷ COP); heat given to the ground = cooling load × (1 + 1 ÷ COP).
Worked example
A house loses 36,000 BTU/h at a design temperature of 5 °F and needs no heat above 70 °F. A heat pump gives 36,000 BTU/h at 47 °F, 24,000 at 17 °F, 20,000 at 5 °F and 16,000 at −5 °F.
At 17 °F the house loses 36,000 × 53 ÷ 65 = 29,354 BTU/h, more than the heat pump gives. At 47 °F it loses 12,738 BTU/h, less. The lines cross at 22.6 °F: that is the balance point.
At 5 °F the heat pump gives 20,000 BTU/h, so the backup heat must give 16,000 BTU/h, which is 4.69 kW. The heat pump covers 55.6% of the design heat loss.
Rules of thumb (rough figures only)
The Rough first figure mode multiplies the floor area by a figure that you choose, such as 30 to 60 BTU/h for each square foot. These figures come from no standard. They ignore insulation, windows, air leaks and climate, so the real heat loss can be half or double. Use them only for a first idea, and never to choose a heat pump.
Limits you should know
- No climate data and no maker data are built in. Type the design temperature for your place and the capacity of the heat pump at each temperature from the maker's table.
- The label capacity is usually at a mild rating point. A heat pump gives less heat when it is colder outside, and less again during defrost.
- The length of a ground loop is not worked out here. It depends on the ground and the hours of running, and is set by a loop design method.
- For radiators that work with the low water temperatures of a heat pump, use the Radiator Sizing Calculator.
- This is a first estimate, not a design. The size of a heat pump for a real building is decided by a professional load calculation, by the method used where you live (for example ACCA Manual J and Manual S in the United States, or EN 12831 and MCS in the United Kingdom). This is not professional advice.