Works on this device

Coefficient of Performance Calculator

Find the coefficient of performance (COP) of a heat pump, a refrigerator or an air conditioner: the heat it moves for each unit of work it takes. Or turn a COP into EER and kW per ton, and back.

Enter your values

COP = useful heat ÷ work put in. For heating the useful heat is the heat given to the warm side; for cooling it is the heat taken from the cold side.

Your values

The power the compressor and the fans take, usually the electrical input.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose COP of a heat pump, refrigerator or air conditioner, then say whether the machine heats or cools.
  2. Choose what to find: the COP, the work put in, or the heat.
  3. Choose rates (kW, BTU/h, tons) or amounts over the same time (kWh, MJ, BTU), and type the figures you know.
  4. Choose Calculate. You get the COP, the heat on the other side by the energy balance, and for cooling the EER and kW per ton.
  5. To change one figure into another unit, choose Convert COP, EER and kW per ton.

The formulas

  • Heating COP (heat pump) = heat given to the warm side ÷ work put in.
  • Cooling COP (refrigerator, air conditioner, chiller) = heat taken from the cold side ÷ work put in.
  • Energy balance: heat given = heat taken + work. So for the same flows, heating COP = cooling COP + 1.
  • EER = COP × 3.412142, because one watt is 3600 ÷ 1055.05585262 = 3.412142 BTU/h. kW per ton = 3.516853 ÷ COP, because one ton of refrigeration is 12,000 BTU/h = 3.516853 kW.
  • Highest possible COP: the Carnot COP from the two temperatures. Work it out in the Carnot Efficiency Calculator.

Worked example

A heat pump gives 10 kW of heat to a house and takes 2.5 kW of electricity. Its heating COP is 10 ÷ 2.5 = 4. By the energy balance it takes 10 − 2.5 = 7.5 kW of heat from the outside air, so the cooling COP of the same flows is 3.

An air conditioner with a COP of 3.5 has an EER of 3.5 × 3.412142 = 11.9425 and needs 3.516853 ÷ 3.5 = 1.00482 kW for each ton of cooling.

SEER, SEER2, HSPF and SCOP

These are seasonal ratings. Each one is the heat moved over a whole test season divided by the electricity used, from several test points weighted for a standard climate. US ratings (SEER, SEER2, HSPF, HSPF2) are in BTU for each watt-hour; dividing by 3.412142 gives the same average in watts for each watt, and the tool shows this.

No factor turns a seasonal rating into the COP at one condition. A European SEER or SCOP (EN 14825) comes from another test with another climate, so it is a different number from a US SEER of the same unit.

Limits you should know

  • The COP changes with the temperatures inside and outside. A figure from one reading is for that moment only; a label figure is for its test conditions.
  • The energy balance assumes steady running with all the work going into the refrigerant. Defrost, standby power and backup heaters change a measured average.
  • For the efficiency of a chiller and its part-load value (IPLV), use the Chiller Efficiency Calculator.