Coefficient of Performance Calculator
Find the coefficient of performance (COP) of a heat pump, a refrigerator or an air conditioner: the heat it moves for each unit of work it takes. Or turn a COP into EER and kW per ton, and back.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose COP of a heat pump, refrigerator or air conditioner, then say whether the machine heats or cools.
- Choose what to find: the COP, the work put in, or the heat.
- Choose rates (kW, BTU/h, tons) or amounts over the same time (kWh, MJ, BTU), and type the figures you know.
- Choose Calculate. You get the COP, the heat on the other side by the energy balance, and for cooling the EER and kW per ton.
- To change one figure into another unit, choose Convert COP, EER and kW per ton.
The formulas
- Heating COP (heat pump) = heat given to the warm side ÷ work put in.
- Cooling COP (refrigerator, air conditioner, chiller) = heat taken from the cold side ÷ work put in.
- Energy balance: heat given = heat taken + work. So for the same flows, heating COP = cooling COP + 1.
- EER = COP × 3.412142, because one watt is 3600 ÷ 1055.05585262 = 3.412142 BTU/h. kW per ton = 3.516853 ÷ COP, because one ton of refrigeration is 12,000 BTU/h = 3.516853 kW.
- Highest possible COP: the Carnot COP from the two temperatures. Work it out in the Carnot Efficiency Calculator.
Worked example
A heat pump gives 10 kW of heat to a house and takes 2.5 kW of electricity. Its heating COP is 10 ÷ 2.5 = 4. By the energy balance it takes 10 − 2.5 = 7.5 kW of heat from the outside air, so the cooling COP of the same flows is 3.
An air conditioner with a COP of 3.5 has an EER of 3.5 × 3.412142 = 11.9425 and needs 3.516853 ÷ 3.5 = 1.00482 kW for each ton of cooling.
SEER, SEER2, HSPF and SCOP
These are seasonal ratings. Each one is the heat moved over a whole test season divided by the electricity used, from several test points weighted for a standard climate. US ratings (SEER, SEER2, HSPF, HSPF2) are in BTU for each watt-hour; dividing by 3.412142 gives the same average in watts for each watt, and the tool shows this.
No factor turns a seasonal rating into the COP at one condition. A European SEER or SCOP (EN 14825) comes from another test with another climate, so it is a different number from a US SEER of the same unit.
Limits you should know
- The COP changes with the temperatures inside and outside. A figure from one reading is for that moment only; a label figure is for its test conditions.
- The energy balance assumes steady running with all the work going into the refrigerant. Defrost, standby power and backup heaters change a measured average.
- For the efficiency of a chiller and its part-load value (IPLV), use the Chiller Efficiency Calculator.