Chiller Efficiency Calculator

Find how much power a chiller uses for each ton of cooling. Enter the cooling it gives (or the chilled water flow and temperatures) and the power it takes, and get kW per ton, COP and EER, or work out the part-load value IPLV or NPLV from the maker's data.

Enter your values

Type the cooling the chiller gives (or the chilled water flow and temperatures) and the power it takes at the same moment.

Your values

The cooling the chiller gives at the same moment, or at the same rating point, as the power you type.

The electrical input power of the chiller (compressor, controls and its own fans) at the same moment as the capacity.

Add it for the efficiency of the whole chilled water plant. Leave it empty for the chiller alone.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose Chiller efficiency to work out the figures from a capacity and a power, Convert to change one figure into the others, or Part-load value for IPLV or NPLV.
  2. For the efficiency, type the cooling capacity in tons, kW or BTU/h. Or choose to work it out from the chilled water flow and the temperatures of the water entering and leaving the chiller.
  3. Type the electrical power the chiller takes at the same moment. Add the power of the pumps and tower fans if you want the figure of the whole plant.
  4. For IPLV or NPLV, type the four figures at 100%, 75%, 50% and 25% load from the maker's data, all in the same unit.
  5. Choose Calculate. You get the results, the working and the formulas.

The formulas

  • kW per ton = power put in (kW) ÷ cooling (tons of refrigeration). Lower is better.
  • COP = cooling ÷ power put in, both in watts. EER = cooling in BTU/h ÷ power put in, in watts. Higher is better.
  • Conversions: EER = COP × 3.412142, kW per ton = 3.516853 ÷ COP, and EER × kW per ton = 12. The factors come from the definitions: 1 BTU = 1055.05585262 J and 1 ton = 12,000 BTU/h.
  • Cooling from the water: flow × density × specific heat × (entering − leaving temperature). For water in US units this is about 500 × gpm × °F in BTU/h.
  • Heat rejected at the condenser = cooling + power put in.
  • IPLV and NPLV (AHRI Standard 550/590): 0.01 A + 0.42 B + 0.45 C + 0.12 D for COP or EER, where A to D are the figures at 100%, 75%, 50% and 25% load. For kW per ton: 1 ÷ (0.01 ÷ A + 0.42 ÷ B + 0.45 ÷ C + 0.12 ÷ D).

Worked example

A chiller gives 500 tons of cooling (1,758.43 kW) and takes 300 kW. Its efficiency is 300 ÷ 500 = 0.6 kW per ton. The COP is 1,758.43 ÷ 300 = 5.86142, and the EER is 12 ÷ 0.6 = 20. The condenser rejects 1,758.43 + 300 = 2,058.43 kW.

The same chiller has 0.58, 0.45, 0.38 and 0.40 kW per ton at 100%, 75%, 50% and 25% load. IPLV = 1 ÷ (0.01 ÷ 0.58 + 0.42 ÷ 0.45 + 0.45 ÷ 0.38 + 0.12 ÷ 0.40) = 0.410714 kW per ton, which is a COP of 8.56278 and an EER of 29.2174.

Limits you should know

  • The efficiency of a chiller changes with its load and with the temperature of the condenser water or the outside air. A figure from one reading is for that moment only.
  • IPLV is for the standard rating conditions. For your own building, NPLV with your design conditions, or the power over your own hours at each load, is closer.
  • No maker data is built in. Take the capacity and the power from the same test or the same moment.
  • For a heat pump or any other machine, the Coefficient of Performance Calculator works out the COP from heat and work. The highest COP that the temperatures allow is in the Carnot Efficiency Calculator.