Refrigeration Capacity Calculator

Find the cooling capacity of a refrigeration system in kW, BTU/h and tons of refrigeration. Use the refrigerant mass flow and the enthalpies from the table of your refrigerant, the displacement of the compressor, or the flow and temperature change of the chilled water, glycol or brine.

Enter your values

Capacity = refrigerant mass flow × refrigeration effect, the rise in enthalpy across the evaporator. Read the enthalpies from the table of your refrigerant.

Your values

At the evaporator outlet (compressor suction), with its superheat. Read it from the property table or the pressure-enthalpy chart of your refrigerant. All the enthalpies must come from the same table, because tables use different starting points.

After the expansion valve. It is the same as the enthalpy of the liquid before the valve (leaving the condenser), because the valve does not change the enthalpy.

At the compressor outlet. With it the tool also gives the compressor work, the COP and the heat rejected.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose how you know the system: the refrigerant mass flow, the compressor displacement, or the flow of a secondary fluid such as chilled water.
  2. For the refrigerant, read the enthalpies from the property table or the pressure-enthalpy chart of your refrigerant: at the evaporator outlet (h1) and after the expansion valve (h4). Add the enthalpy at the compressor outlet (h2) for the work and the COP of the cycle.
  3. For a fluid, type its flow and how much it is cooled. The density and the specific heat are under More options.
  4. Choose whether to find the capacity or the flow needed for a capacity, then choose Calculate.

The formulas

  • Refrigeration effect = h1 − h4: the heat each kilogram of refrigerant takes up in the evaporator.
  • Capacity = refrigerant mass flow × (h1 − h4).
  • Compressor: mass flow = displacement × volumetric efficiency ÷ specific volume at suction.
  • Cycle: compressor work = mass flow × (h2 − h1); heat rejected = mass flow × (h2 − h4); COP = (h1 − h4) ÷ (h2 − h1).
  • Secondary fluid: capacity = flow × density × specific heat × temperature change. For water in US units, about 500 × gpm × °F in BTU/h.
  • Ton of refrigeration = 12,000 BTU/h = 3.516853 kW, by definition.

Worked example

A refrigerant leaves the evaporator at h1 = 400 kJ/kg and enters it at h4 = 250 kJ/kg, so the refrigeration effect is 150 kJ/kg. A mass flow of 0.07 kg/s gives 0.07 × 150 = 10.5 kW, which is 35,827.5 BTU/h or 2.98562 tons.

If the vapour leaves the compressor at h2 = 435 kJ/kg, the compressor gives 0.07 × 35 = 2.45 kW to the vapour, the condenser rejects 12.95 kW, and the COP of the cycle is 150 ÷ 35 = 4.28571.

Limits you should know

  • No refrigerant table is built in. Take every enthalpy and the specific volume from one table or chart of your refrigerant, at your pressures and temperatures.
  • The cycle work is the work given to the vapour. The electrical power of the compressor is higher, by the losses of the motor and the compressor.
  • The capacity of the cycle is not the cooling a room or a product gets: pipes and fans add heat.
  • For kW per ton, COP and EER of a chiller, use the Chiller Efficiency Calculator. For the COP of any heat pump or air conditioner, use the Coefficient of Performance Calculator.