Cooling Tower Calculator
Work out what a cooling tower does: its range, approach and effectiveness, the heat it rejects in BTU/h, kW and tons, the water flow for a heat load, and the water it loses by evaporation, drift and blowdown.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose Range, approach, effectiveness and heat rejected and type the hot and cold water temperatures, the wet-bulb temperature of the air and the water flow.
- Choose Water flow for a heat load and a range to find the flow for a heat you know, or for a chiller from its cooling and its input power.
- Choose Water balance for the evaporation, the drift, the blowdown and the make-up water. Type the cycles of concentration, or two measurements of the circulating and the make-up water.
- Choose Calculate. You get the results, a table and the working.
The formulas
- Range = hot water in − cold water out. Approach = cold water out − wet-bulb temperature. Effectiveness = range ÷ (range + approach).
- Heat rejected = water flow × density × specific heat × range. For water in US units, about 500 × gpm × °F in BTU/h. One ton of refrigeration is 12,000 BTU/h.
- Cooling tower ton: a trade convention, often 15,000 BTU/h (the cooling of the chiller plus the heat of its compressor). You can change it.
- Heat from a chiller = its cooling + its input power.
- Evaporation (heat balance estimate) = share of the heat removed by evaporation × flow × specific heat × range ÷ latent heat. With 85% and 1,000 BTU/lb this is the common rule 0.00085 × flow × range (°F).
- Blowdown = evaporation ÷ (cycles − 1) − drift. Make-up = evaporation + drift + blowdown = evaporation × cycles ÷ (cycles − 1).
- Cycles of concentration = concentration in the circulating water ÷ concentration in the make-up water.
Worked example
Water enters a tower at 95 °F and leaves at 85 °F, with a wet-bulb temperature of 78 °F. The range is 10 °F, the approach 7 °F and the effectiveness 10 ÷ 17 = 58.8%.
With 1,000 gpm the tower rejects about 500.6 × 1,000 × 10 = 5,006,290 BTU/h, which is 417.19 tons of refrigeration or 333.75 cooling tower tons.
At 4 cycles of concentration, with 85% of the heat removed by evaporation at 1,000 BTU/lb and a drift of 0.005%, the tower evaporates 8.498 gpm, loses 0.05 gpm as drift and needs 2.783 gpm of blowdown, so the make-up water is 11.33 gpm.
Limits you should know
- The evaporation is an estimate. The share of the heat removed by evaporation changes with the weather; in cold, dry air it is lower. A water meter on the make-up and the blowdown gives the real figures.
- The tool does not predict how a tower performs at another wet-bulb temperature or flow. That comes from the maker's performance curves.
- No climate data is built in. Take the design wet-bulb temperature for your place from design data.
- The selection of a cooling tower is made from the maker's data for your duty and design conditions. A professional design by the method used where you work decides the size.
- For the efficiency of the chiller, use the Chiller Efficiency Calculator.