Log Mean Temperature Difference Calculator
Work out the log mean temperature difference (LMTD) of a heat exchanger from the inlet and outlet temperatures of the hot and cold fluids. You can also get the heat rate Q = U × A × LMTD, the area or U, and the correction factor F of a shell-and-tube exchanger.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose counterflow or parallel flow, or a shell-and-tube exchanger with its number of shell passes.
- Enter the inlet and outlet temperatures of the hot fluid and of the cold fluid, in °C, °F or K.
- Choose what to find: the mean temperature difference only, the heat rate, the area needed, or U. Then enter the other two of Q, U and A.
- Choose Calculate. The result shows ΔT at each end, the LMTD, F where it applies, and the working.
The formulas
- LMTD: (ΔT1 − ΔT2) ÷ ln(ΔT1 ÷ ΔT2). When ΔT1 = ΔT2, the LMTD is that same difference.
- Counterflow: ΔT1 = Th,in − Tc,out and ΔT2 = Th,out − Tc,in. Parallel flow: ΔT1 = Th,in − Tc,in and ΔT2 = Th,out − Tc,out.
- Heat rate: Q = U × A × F × LMTD, so A = Q ÷ (U × F × LMTD) and U = Q ÷ (A × F × LMTD). F = 1 for pure counterflow and parallel flow.
- Shell and tube, one shell pass and 2, 4, 6 … tube passes: with P = (tc,out − tc,in) ÷ (Th,in − tc,in) and R = (Th,in − Th,out) ÷ (tc,out − tc,in), F = √(R² + 1) × ln((1 − P) ÷ (1 − P R)) ÷ ((R − 1) × ln[(2 − P (R + 1 − √(R² + 1))) ÷ (2 − P (R + 1 + √(R² + 1)))]) (Bowman, Mueller and Nagle). For N shells in series, the same with the P of one shell.
Worked examples
Counterflow: the hot fluid goes from 150 °C to 90 °C and the cold fluid from 30 °C to 70 °C. ΔT1 = 150 − 70 = 80 K and ΔT2 = 90 − 30 = 60 K, so LMTD = 20 ÷ ln(80 ÷ 60) = 69.5212 K. With U = 500 W/(m²·K) and A = 10 m², Q = 500 × 10 × 69.5212 = 347.606 kW.
The same temperatures in parallel flow: ΔT1 = 150 − 30 = 120 K and ΔT2 = 90 − 70 = 20 K, so LMTD = 100 ÷ ln 6 = 55.8111 K, which is lower.
In a shell-and-tube exchanger with one shell pass: P = 40 ÷ 120 = 0.333333 and R = 60 ÷ 40 = 1.5, so F = 0.910481 and the mean difference is 0.910481 × 69.5212 = 63.2977 K.
With the hot fluid cooled to 60 °C and the cold fluid warmed to 100 °C, one shell pass cannot do it (the temperatures cross). Two shell passes give F = 0.794607, and 350 kW at U = 500 W/(m²·K) needs 22.5003 m².
Limits you should know
- U and the specific heats are taken as the same along the whole exchanger, with no heat lost to the outside. If they change a lot, split the exchanger into parts.
- F is given for shell-and-tube exchangers with N shell passes and 2N (or an even multiple of N) tube passes. Cross-flow and plate exchangers have other F charts that are not built in.
- Each fluid is taken as one phase, or as condensing or boiling at one temperature. A fluid that cools as a gas and then condenses needs the exchanger split into zones.
- U is your figure. To build it from the films and the wall, see the Convection Calculator and the Thermal Resistance Calculator.
- This is arithmetic for learning and checking, not a heat exchanger design.