Sensible Heat Calculator
Work out sensible heat, the heat that changes a temperature without melting, boiling or condensing. Use it for a batch of any material, for a flowing liquid or gas, or for an air flow, where the tool shows the 1.08 × cfm × ΔT rule beside the exact moist air form.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose a batch (a mass warmed or cooled), a flow (a liquid or gas through a coil or heater), or an air flow.
- Choose what to find: the heat, the mass or flow, the specific heat, or a temperature.
- Enter the other values. The menu fills in example specific heats of common materials; use your own figure when it matters. For air, the temperature, humidity and height are under More options.
- Choose Calculate. The result shows the answer, the temperature change and the working.
The formulas
- Batch: Q = m × cp × (T2 − T1). A positive Q warms the material; a negative Q cools it.
- Flow: Q̇ = ṁ × cp × (Tout − Tin), with ṁ = volume flow × density.
- Air, exact form: Q̇ = flow × (cp ÷ v) × ΔT, with cp = 1006 + 1860 × W J/(kg·K) for each kg of dry air and v the specific volume of the moist air.
- Air, the 1.08 rule: Q (BTU/h) = 1.08 × cfm × ΔT (°F). It takes standard air: 0.075 lb/ft³ × 0.24 BTU/(lb·°F) × 60 min/h = 1.08.
Worked examples
10 kg of water (cp = 4.186 kJ/(kg·K)) warmed from 20 °C to 80 °C takes Q = 10 × 4.186 × 60 = 2,511.6 kJ, which is about 0.6977 kWh.
2 m³/h of water (1,000 kg/m³) heated from 10 °C to 70 °C: ṁ = 2 ÷ 3,600 × 1,000 = 0.555556 kg/s, so Q̇ = 0.555556 × 4.186 × 60 = 139.533 kW.
1,000 cfm of air warmed by 20 °F: the rule gives 1.08 × 1,000 × 20 = 21,600 BTU/h. With air at 68 °F, 50% relative humidity and sea level, the exact factor is 1.08558, so Q = 21,711.6 BTU/h, about 0.52% more than the rule.
Limits you should know
- Sensible heat only. Melting, boiling, condensing and the moisture taken out at a cooling coil are latent heat: see the Latent Heat Calculator.
- cp is taken as constant over the temperature range; use a mean value. The example specific heats are rounded table values, not data for your product.
- For the heating or cooling load of a room or a house, see the BTU Calculator; for the air flow a room needs, the Room Cfm Calculator; for specific heat itself, the Specific Heat Calculator.
- This is arithmetic for learning, planning and checking, not an equipment selection.