Sensible Heat Calculator

Work out sensible heat, the heat that changes a temperature without melting, boiling or condensing. Use it for a batch of any material, for a flowing liquid or gas, or for an air flow, where the tool shows the 1.08 × cfm × ΔT rule beside the exact moist air form.

Enter your values

The sensible heat of a batch of any material, or the mass, specific heat or end temperature.

Your values

4.186 kJ/(kg·K) is the usual figure for liquid water. The menu fills in other examples.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

How to use this calculator

  1. Choose a batch (a mass warmed or cooled), a flow (a liquid or gas through a coil or heater), or an air flow.
  2. Choose what to find: the heat, the mass or flow, the specific heat, or a temperature.
  3. Enter the other values. The menu fills in example specific heats of common materials; use your own figure when it matters. For air, the temperature, humidity and height are under More options.
  4. Choose Calculate. The result shows the answer, the temperature change and the working.

The formulas

  • Batch: Q = m × cp × (T2 − T1). A positive Q warms the material; a negative Q cools it.
  • Flow: Q̇ = ṁ × cp × (Tout − Tin), with ṁ = volume flow × density.
  • Air, exact form: Q̇ = flow × (cp ÷ v) × ΔT, with cp = 1006 + 1860 × W J/(kg·K) for each kg of dry air and v the specific volume of the moist air.
  • Air, the 1.08 rule: Q (BTU/h) = 1.08 × cfm × ΔT (°F). It takes standard air: 0.075 lb/ft³ × 0.24 BTU/(lb·°F) × 60 min/h = 1.08.

Worked examples

10 kg of water (cp = 4.186 kJ/(kg·K)) warmed from 20 °C to 80 °C takes Q = 10 × 4.186 × 60 = 2,511.6 kJ, which is about 0.6977 kWh.

2 m³/h of water (1,000 kg/m³) heated from 10 °C to 70 °C: ṁ = 2 ÷ 3,600 × 1,000 = 0.555556 kg/s, so Q̇ = 0.555556 × 4.186 × 60 = 139.533 kW.

1,000 cfm of air warmed by 20 °F: the rule gives 1.08 × 1,000 × 20 = 21,600 BTU/h. With air at 68 °F, 50% relative humidity and sea level, the exact factor is 1.08558, so Q = 21,711.6 BTU/h, about 0.52% more than the rule.

Limits you should know

  • Sensible heat only. Melting, boiling, condensing and the moisture taken out at a cooling coil are latent heat: see the Latent Heat Calculator.
  • cp is taken as constant over the temperature range; use a mean value. The example specific heats are rounded table values, not data for your product.
  • For the heating or cooling load of a room or a house, see the BTU Calculator; for the air flow a room needs, the Room Cfm Calculator; for specific heat itself, the Specific Heat Calculator.
  • This is arithmetic for learning, planning and checking, not an equipment selection.