Psychrometric Calculator
Moist air is dry air with water vapour in it. When you know the pressure and two values, such as the temperature and the relative humidity, every other property follows. Choose what you know and this page works out the rest, with the formulas and your numbers.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose the button below them.
Your result
How it was worked out
How to use this calculator
- Choose what you know. The first choice works from the dry-bulb temperature and the relative humidity.
- Enter the values and pick the units. Temperatures can be in °C, °F or K.
- Enter the pressure at your place, or leave it empty and enter your height above sea level.
- Choose Calculate. The result lists every property. Results in SI units also have a line in inch-pound units, such as grains per pound and Btu per pound.
- Other choices mix two air streams, work out a heating, cooling or humidifying step, give the air density, give the vapour pressure of water, and draw the lines of a psychrometric chart.
The formulas
- Vapour pressure: e = RH ÷ 100 × es(t). The saturation vapour pressure is the Buck equation (1996): es = 6.1121 × exp((18.678 − t ÷ 234.5) × t ÷ (257.14 + t)) hPa, with t in °C.
- Humidity ratio: W = 0.62197 × e ÷ (p − e), in kg of water vapour for each kg of dry air. Specific humidity = W ÷ (1 + W).
- Absolute humidity = e ÷ (Rv × T), with Rv = 461.523 J/(kg·K) and T in kelvin.
- Enthalpy: h = 1.006 × t + W × (2501 + 1.86 × t) kJ for each kg of dry air.
- Specific volume = Rd × T ÷ (p − e) for each kg of dry air, with Rd = 287.05287 J/(kg·K). Density = (p − e) ÷ (Rd × T) + e ÷ (Rv × T).
- Wet-bulb temperature: the value tw that makes e = es(tw) − 0.000662 × p × (t − tw) true. Dew point: the temperature at which es equals e.
- Mixing: W and h of the mix are averages weighted by the mass flow of dry air of each stream.
- A heating or cooling step: total heat = m × (h₂ − h₁), and water added = m × (W₂ − W₁), where m is the mass flow of dry air.
Worked examples
Air at 25 °C and 50% relative humidity at 1013.25 hPa: e = 15.843 hPa. The humidity ratio is 9.879 g/kg (69.16 grains per pound), the absolute humidity is 11.51 g/m³, the enthalpy is 50.32 kJ/kg, the specific volume is 0.8581 m³/kg and the density is 1.177 kg/m³. The wet bulb is 17.9 °C and the dew point is 13.9 °C.
Mixing: 1,000 m³/h of outside air at 32 °C and 40% joins 3,000 m³/h of return air at 24 °C and 50%. The outside air is 24.4% of the dry air. The mix is at 26.0 °C and 47.5%, with a humidity ratio of 9.934 g/kg.
Cooling: 1,000 m³/h of air at 25 °C and 50% leaves a cooling coil at 13 °C and 95%. The coil takes out 4.81 kW in total: 3.98 kW of sensible heat and 0.84 kW of latent heat. It drains 1.19 kg of water each hour. The sensible heat ratio is 0.83.
Air density: at 25 °C, 50% and 1013.25 hPa the density is 1.1769 kg/m³, which is 96.1% of the standard sea-level density. The density altitude is 415 m.
Pages for the jobs next to this one
- Relative humidity alone, with tables for wet and dry bulbs: Relative Humidity Calculator.
- The dew point, frost point, condensation and pressure dew point: Dew Point Calculator.
- The wet-bulb temperature and the wet-bulb globe temperature (WBGT): Wet Bulb Calculator.
- The heat index and the humidex: Heat Index Calculator.
Limits you should know
- Moist air is treated as an ideal gas mixture. The small correction for real air (about 0.4% at sea level) is not applied, so values can differ in the third digit from tables that apply it.
- The wet bulb here is the wet bulb of a ventilated psychrometer. The thermodynamic wet-bulb temperature of the ASHRAE handbook differs from it by less than 0.3 °C between 0 and 50 °C.
- The enthalpy in Btu per pound uses the inch-pound formula, whose zero is dry air at 0 °F. The SI value has its zero at 0 °C. So the two do not convert by a factor alone.
- Temperatures from −80 °C to 100 °C and pressures from 10 hPa to 2,000 hPa are accepted. The Buck equation is given by its author for −80 to 50 °C and stays within about 0.1% of the Goff and Gratch formula up to 100 °C.
- The mixing option does not work out a mix that ends above saturation, where fog forms.
- The step option does not count the heat of the water that is added or drained, and it does not find the apparatus dew point of a coil.
- The chart option draws lines of relative humidity only.
- The vapour pressure option is for water. It has no data for other liquids or gases.
- Results are for study and first estimates. The design of a heating, cooling or drying system needs a qualified engineer and the standards of your country.