Relative humidity tells you how close the air is to holding all the water vapour it can at its temperature. Choose what you measured, enter the readings with their units, and get the relative humidity with the working.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose the button below them.
Your result
How it was worked out
How to use this calculator
- Choose what you want to calculate. The first choice works from the air temperature and the dew point of a weather report.
- For a sling psychrometer or a pair of wet and dry thermometers, choose Relative humidity from dry-bulb and wet-bulb readings.
- Enter the readings and pick a unit for each one: °C, °F or K.
- When the pressure matters, enter the pressure at your place, or leave it empty and enter your height above sea level.
- Choose Calculate. Under How it was worked out you see each formula with your numbers.
The formulas
- Relative humidity = e ÷ es × 100. Here e is the vapour pressure of the water in the air, and es is the saturation vapour pressure at the air temperature.
- Saturation vapour pressure (Buck equation, 1996): es = 6.1121 × exp((18.678 − t ÷ 234.5) × t ÷ (257.14 + t)) hPa, with t in °C, over liquid water.
- From a dew point: e is the saturation vapour pressure at the dew point.
- From wet and dry bulbs (psychrometer relation): e = es(tw) − A × p × (t − tw). A is 0.000662 per kelvin for a ventilated psychrometer, and p is the air pressure.
- From absolute humidity: e = ρ × Rv × T, with Rv = 461.523 J/(kg·K) and T in kelvin.
- From a mixing ratio w in kg per kg of dry air: e = w × p ÷ (0.62197 + w).
- After heating or cooling: the vapour pressure stays the same, so RH₂ = RH₁ × es(t₁) ÷ es(t₂).
Worked examples
The air is at 25 °C and the dew point is 15 °C. The saturation vapour pressure is 31.685 hPa at 25 °C and 17.052 hPa at 15 °C. Relative humidity = 17.052 ÷ 31.685 × 100 = 53.8%.
A sling psychrometer reads 25 °C dry and 18 °C wet at 1013.25 hPa. e = 20.639 − 0.000662 × 1013.25 × 7 = 15.944 hPa. Relative humidity = 15.944 ÷ 31.685 × 100 = 50.3%, and the dew point is 14.0 °C.
Outside air at 5 °C and 80% is heated to 21 °C indoors. Its relative humidity falls to 28.1%, because warm air can hold more water vapour.
Air at 25 °C and 50% holds 11.51 g of water vapour in each cubic metre. Its mixing ratio at sea-level pressure is 9.879 g for each kilogram of dry air.
Constants this page uses
| Constant | Value | Source |
|---|---|---|
| Buck equation over water | 6.1121, 18.678, 234.5, 257.14 | Buck (1996) |
| Buck equation over ice | 6.1115, 23.036, 333.7, 279.82 | Buck (1996) |
| Gas constant of water vapour | 461.523 J/(kg·K) | 8.314462618 J/(mol·K) ÷ 0.01801528 kg/mol |
| Gas constant of dry air | 287.05287 J/(kg·K) | ISO 2533:1975 standard atmosphere |
| Ratio of molar masses, water to dry air | 0.62197 | The two gas constants above |
| Psychrometer coefficient, ventilated | 0.000662 per K | FAO Irrigation and Drainage Paper 56 (1998) |
| Psychrometer coefficient, natural ventilation | 0.000800 per K | FAO Irrigation and Drainage Paper 56 (1998) |
| Psychrometer coefficient, still air indoors | 0.001200 per K | FAO Irrigation and Drainage Paper 56 (1998) |
Pages for the jobs next to this one
- The dew point itself, the frost point and condensation on a cold surface: Dew Point Calculator.
- The wet-bulb temperature from temperature and humidity: Wet Bulb Calculator.
- Enthalpy, air density and every other property of moist air: Psychrometric Calculator.
- A quick change between dew point, humidity and temperature: Weather Dew Point Converter.
Limits you should know
- Relative humidity is given over liquid water, also below 0 °C. That is how weather services report it. Below 0 °C the page adds the value over ice.
- The Buck equation is given by its author for −80 to 50 °C. From 0 to 100 °C it is within about 0.1% of the older Goff and Gratch formula. Over liquid water below −40 °C the values are rough.
- Temperatures from −80 °C to 100 °C are accepted. Pressures from 10 hPa to 2,000 hPa are accepted.
- The pressure from a height uses the standard atmosphere (ISO 2533). The real pressure at your place changes with the weather by a few percent, so a measured station pressure is better.
- A wet bulb only reads right when its wick is clean, wet and in moving air. Choose the psychrometer type that matches your instrument.
- Air is treated as an ideal gas mixture. The small correction for real air (about 0.4% at sea level) is not applied.
- This page uses the readings you type. It does not fetch weather data and it is not a forecast.