Boiler Efficiency Calculator
Find how much of the heat in the fuel a boiler turns into useful heat. Use the direct method with the steam or hot water output and the fuel used, the indirect method with the losses from a test, or a flue gas reading for the combustion efficiency.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose Direct method when you can measure the useful heat and the fuel over the same time. Give the output as a figure, as steam (flow and enthalpies from a steam table) or as hot water (flow and temperatures). Give the input as a figure, or as the fuel flow and its heating value.
- Choose Fuel use to find how much fuel a boiler burns for a heat output at a known efficiency, by mass, by volume of oil or by volume of gas.
- Choose Indirect method when you have the losses from a boiler test. Type each loss as a percent of the fuel heat input.
- Choose Combustion efficiency when you have a flue gas analyser reading. Type the flue gas and air temperatures, the O₂ or CO₂ reading, and the Siegert constants of your fuel (or pick a labelled example).
- Say whether the heating value is gross or net. Then choose Calculate.
The formulas
- Direct method: efficiency = useful heat output ÷ fuel heat input × 100.
- Steam output = steam flow × (enthalpy of the steam − enthalpy of the feed water). Hot water output = flow × density × specific heat × (supply − return).
- Fuel input = fuel flow × heating value. Turned round: fuel use = useful output ÷ efficiency ÷ heating value.
- Indirect method: efficiency = 100% − the sum of the losses (flue gas, water from hydrogen, moisture, carbon monoxide, radiation and convection, unburnt fuel).
- Siegert formula: flue gas loss = (flue gas temperature − air temperature) × (A2 ÷ (21 − O₂) + B), or with CO₂: × (A1 ÷ CO₂ + B). Combustion efficiency = 100% − flue gas loss.
- Excess air from oxygen: λ = 21 ÷ (21 − O₂); excess air = (λ − 1) × 100%.
Worked example
A steam boiler makes 2,000 kg/h of steam at 2,780 kJ/kg from feed water at 440 kJ/kg. The useful output is 2,000 × (2,780 − 440) ÷ 3,600 = 1,300 kW. It burns 115 kg/h of oil with a gross heating value of 45 MJ/kg, an input of 1,437.5 kW. The efficiency is 1,300 ÷ 1,437.5 = 90.43%, and the evaporation ratio is 17.39 kg of steam for each kg of fuel.
Turned round: to give 1,300 kW at an efficiency of 85% the boiler needs 1,300 ÷ 0.85 = 1,529.41 kW of fuel. With oil of 45 MJ/kg that is 122.353 kg/h, and at a density of 0.84 kg/L it is 145.658 L/h.
A gas boiler has flue gas at 350 °F (176.667 °C), air at 68 °F (20 °C) and 3.5% oxygen. With the example constants for natural gas (A2 = 0.66, B = 0.009), the flue gas loss is 156.667 × (0.66 ÷ 17.5 + 0.009) = 7.32%, so the combustion efficiency is 92.7% with 20% excess air.
Limits you should know
- Gross and net heating values give different efficiencies for the same boiler. Always say which one you used. On the net value a condensing boiler can show more than 100%.
- The Siegert formula gives the flue gas loss only. It leaves out carbon monoxide, casing and standing losses, and it does not fit a condensing boiler while it condenses.
- The fuel constants and the example losses are labelled examples. Use the figures of your fuel, your test code and your analyser.
- A seasonal efficiency (such as AFUE or SEDBUK) comes from a standard test with part-load and standing losses; this tool does not work it out.
- For the size of a boiler for a house, work out the heat loss with the BTU Calculator. For the running cost, use the Heating Cost Calculator.