Cooling Load Calculator
Type the walls, roof and windows of a room with the sun on them, the outside design weather, the air that comes in, and the people, lights and equipment. You get the cooling load in kW, BTU/h and tons, its sensible and latent parts, and the share of every gain.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to work out a cooling load
- Choose Cooling load of a room or building, or start from an example.
- List the walls, roof and windows with their area, U-value, the sun on them at the peak hour and their solar absorptance (or the SHGC of glass).
- Type the inside and outside design temperatures (with the outside wet-bulb), the air leaking in and the fresh air, and the people, lights and equipment.
- Press Calculate. To see how a cooling unit of a given size copes over a hot day, with the heat stored in the building, use the box under the result.
How the load is found
- Walls and roofs: Q = U × A × (Tsa − Ti), with the sol-air temperature Tsa = To + α × I ÷ ho (less the loss of a roof to the sky).
- Glass: Q = U × A × (To − Ti) + SHGC × A × I.
- Air from outside: sensible m × cp × (To − Ti) and latent m × (Wo − Wi) × hfg, with the humidity of the outside air from its wet-bulb temperature.
- People, lights and equipment: the heat you type. Fresh air from the ventilation loads the cooling unit, not the room.
- 1 kW = 3,412 BTU/h; one ton of refrigeration = 12,000 BTU/h = 3.517 kW.
Worked example
A 60 m² office with sun on a south and a west wall, a roof and 13 m² of windows, 6 people, 600 W of lights, 1,200 W of equipment and 60 L/s of fresh air, at 35 °C outside (24 °C wet-bulb) and 24 °C inside, needs about 8.5 kW (2.4 tons): 6.9 kW sensible and 1.5 kW latent. The sun through the glass is the largest part.
A coil cooling 3,000 m³/h of air from 27 °C, 50% to 13 °C, 95% removes 19.3 kW and condenses about 7.9 litres of water each hour.
Limits you should know
- The room mode adds every gain at its peak at the same time and leaves out the heat stored in the walls, so it is on the high side. The simulation in the box below counts the storage.
- No climate data, U-values or heat gain tables are built in: the hints say where to find them. Cold rooms (goods to cool and doors), the CLTD and RTS procedures and Manual J are not covered.
- This is an estimate, not a design: equipment for a real building is sized by a professional load calculation.