Cooling Load Calculator

Type the walls, roof and windows of a room with the sun on them, the outside design weather, the air that comes in, and the people, lights and equipment. You get the cooling load in kW, BTU/h and tons, its sensible and latent parts, and the share of every gain.

Enter your values

The heat that comes in on the hottest design hour: through walls, roof and glass, with the sun, with outside air, and from people, lights and equipment.

Your values

The hot design temperature for your place, for example the 0.4% cooling dry-bulb of the ASHRAE climate data. No climate figure is built in.

The mean coincident wet-bulb of the same climate data. It sets how damp the outside air is.

Needed for surfaces of the kind "To a space that is not cooled" (a corridor, an attic or a garage).

Infiltration: how many times each hour the room air is replaced by outside air that leaks in. From a test or your own figure.

Outside air that the cooling unit brings in and cools, for example 10 L/s for each person where the code asks for it. It loads the cooling unit, not the room.

Depends on the activity. ASHRAE Handbook—Fundamentals (chapter 18, table 1) lists heat gains from people; 75 W sensible and 55 W latent are its figures for moderately active office work.

Computers, screens, printers, a kitchen: the power they use at the same time.

Walls, roof and windows

Sun: the solar radiation on the surface at the hour you plan for, from solar data for your place and its direction (0 or empty in the shade). α: about 0.3 to 0.5 for light colours and 0.8 to 0.95 for dark ones. SHGC: from the window label.

This unit is used in every row.

This unit is used in every row.

This unit is used in every row.

More options

Cooking, kettles, open water: from the maker or a heat gain table.

An extra share for uncertainty, if your method uses one.

Sets the air pressure (standard atmosphere, ISO 2533).

The sol-air temperature of the ASHRAE Handbook—Fundamentals uses 17 W/(m²·K) (3.0 BTU/(h·ft²·°F)).

A roof also loses heat to the sky. The ASHRAE Handbook—Fundamentals uses 3.9 K (7 °F) for horizontal surfaces and 0 for walls.

Used only by the hour-by-hour simulation in the box below: heat capacity per floor area of EN ISO 13790:2008, Table 12.

Used only by the simulation. Leave it empty to try the sensible room load worked out here.

Warmest (at the design temperature, 15:00) minus coolest (03:00), from the climate data. Used only by the simulation.

Used only by the simulation; 0 to 24 for all day.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

Hour-by-hour design day simulation

Hour-by-hour design day simulation

Uses the room of Cooling load of a room or building above, with the construction, the cooling unit, the daily range and the occupied hours under More options. The server simulates three identical hot days, hour by hour, with the room air and the heat stored in the building: the room temperature, the cooling the unit delivers and when the room gets too warm. You get a plot, the values every 15 minutes and CSV and JSON files.

The calculator above works on your device. When you run a task in this section, Toolvito receives the values and result you submit to make the file or run the check. Download the result within one hour after the job finishes. Choose Delete files now to request earlier removal. The hourly cleanup normally removes files within one to two hours after completion.

How to work out a cooling load

  1. Choose Cooling load of a room or building, or start from an example.
  2. List the walls, roof and windows with their area, U-value, the sun on them at the peak hour and their solar absorptance (or the SHGC of glass).
  3. Type the inside and outside design temperatures (with the outside wet-bulb), the air leaking in and the fresh air, and the people, lights and equipment.
  4. Press Calculate. To see how a cooling unit of a given size copes over a hot day, with the heat stored in the building, use the box under the result.

How the load is found

  • Walls and roofs: Q = U × A × (Tsa − Ti), with the sol-air temperature Tsa = To + α × I ÷ ho (less the loss of a roof to the sky).
  • Glass: Q = U × A × (To − Ti) + SHGC × A × I.
  • Air from outside: sensible m × cp × (To − Ti) and latent m × (Wo − Wi) × hfg, with the humidity of the outside air from its wet-bulb temperature.
  • People, lights and equipment: the heat you type. Fresh air from the ventilation loads the cooling unit, not the room.
  • 1 kW = 3,412 BTU/h; one ton of refrigeration = 12,000 BTU/h = 3.517 kW.

Worked example

A 60 m² office with sun on a south and a west wall, a roof and 13 m² of windows, 6 people, 600 W of lights, 1,200 W of equipment and 60 L/s of fresh air, at 35 °C outside (24 °C wet-bulb) and 24 °C inside, needs about 8.5 kW (2.4 tons): 6.9 kW sensible and 1.5 kW latent. The sun through the glass is the largest part.

A coil cooling 3,000 m³/h of air from 27 °C, 50% to 13 °C, 95% removes 19.3 kW and condenses about 7.9 litres of water each hour.

Limits you should know

  • The room mode adds every gain at its peak at the same time and leaves out the heat stored in the walls, so it is on the high side. The simulation in the box below counts the storage.
  • No climate data, U-values or heat gain tables are built in: the hints say where to find them. Cold rooms (goods to cool and doors), the CLTD and RTS procedures and Manual J are not covered.
  • This is an estimate, not a design: equipment for a real building is sized by a professional load calculation.